Southwire 55528302, Metal Clad Cable 10 AWG 3C with Ground Solid Copper THHN Green Armor
Description
Southwire 55528302 is an MC-AP™ HCF all purpose health care facility Type MC cable with three 10 AWG solid copper conductors, insulated Type THHN/THWN in black, red and white, a green insulated ground and a bare 8000 series aluminum grounding/bonding conductor, all under green aluminum interlocked armor. The green that identifies the cable is the armor's; the insulated ground is also green. Conductors are rated 90°C dry.
Southwire 55528302 Technical Specs
Conductors and Insulation
| Conductor Size | 10 AWG |
|---|---|
| Number of Conductors | 3, plus two grounding conductors |
| Conductor | Solid copper |
| Conductor Colors | Black, Red, White |
| Insulation | PVC with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 25 mils (0.64 mm) |
| Diameter Over Conductor | 0.101 in (0.26 cm) |
Grounding and Armor
| Grounding | Green insulated, PVC with nylon sheath, Type THHN/THWN, with redundant grounding by a bare 8000 series aluminum grounding/bonding conductor and the armor; the armor is in contact with the aluminum conductor |
|---|---|
| Binder | Mylar tape, with a print legend wrapped around the assembly |
| Armor | Green aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.619 in (1.57 cm) |
|---|---|
| Approximate Weight | 210 lbs per 1,000 ft (313 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry, Type THHN/THWN |
|---|
Standards
| ASTM B3 | Soft or annealed copper wire |
|---|---|
| UL 83 | Thermoplastic insulated wires and cables |
| UL 1569 | Metal-clad cables |
| UL 1479 | Fire tests of penetration firestops |
| UL 1685 FT4 | Vertical-tray fire propagation and smoke release test |
| IEEE 1202 FT4 | Flame test (70,000) BTU/hr vertical tray test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 55528302 Applications
- Branch-circuit wiring for patient care areas of hospitals, medical centers and other health care facilities, including nursing homes, dental offices, clinics and outpatient facilities, when installed in accordance with NEC Articles 517 and 330 and mechanically protected per Article 300.4. Use in classified anesthetizing areas is prohibited.
- Circuits requiring redundant, dedicated or isolated grounding paths.
- Fishing through or embedding in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
- Use with UL Listed MCI-A fittings.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.