Southwire 55541399 is a 14 AWG, three-conductor armored cable rated 600 V. Its 7-strand compressed bare copper conductors carry 30 mils of cross-linked polyethylene (XLPE) insulation, with one 14 AWG copper grounding conductor. Aluminum interlocked armor (AIA) and a polyvinyl chloride (PVC) outer jacket complete the cable.
Southwire 55541399 Technical Specs
Conductors & Insulation
| Conductor Size | 14 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 7 |
| Conductor | 7-strand Class B compressed bare copper per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE) |
| Insulation Thickness | 30 mils (0.76 mm) |
| Conductor Colors | Black, red, blue |
Grounding, Armor & Jacket
| Grounding Conductor | One 14 AWG copper |
|---|---|
| Filler | Polypropylene |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 0.530 in (1.35 cm) |
| Outer Jacket | Polyvinyl chloride (PVC) |
| Jacket Thickness | 50 mils (1.27 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 0.640 in (1.63 cm) |
|---|---|
| Approximate Weight | 199 lbs/1000 ft (296 kg/km) |
| Copper Weight | 51 lbs/1000 ft (76 kg/km) |
| Minimum Bend Radius | 4.5 in (11.43 cm) |
Electrical Characteristics
| DC Resistance at 25°C (ohms/1000 ft) | 2.631 |
|---|---|
| AC Resistance at 75°C (ohms/1000 ft) | 3.170 |
| Allowable Ampacity in Raceway, 75°C | 20 |
| Allowable Ampacity in Raceway, 90°C | 25 |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Location Rating | Class I, II, and III, Division 2 per NEC Article 501 and 502 |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1569 Metal-Clad Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
- ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Southwire 55541399 Applications
- Wet and dry areas, conduits, ducts, troughs and trays.
- Direct burial and aerial runs supported by a messenger.