Southwire 56177804, Armored Cable 14 AWG 25C Copper 600 V Black
Southwire · MPN 56177804
Description
Southwire 56177804 is a 14 AWG, 25-conductor Type TECK 90 armored control cable rated 600 V. Its 7-strand copper conductors carry 30 mils of cross-linked polyethylene (XLPE), black and numbered, with one 14 AWG uninsulated copper grounding conductor. A black PVC inner jacket, aluminum interlocked armor (AIA) and a black PVC outer jacket complete the cable.
Southwire 56177804 Technical Specs
Conductors & Insulation
| Conductor Size | 14 AWG |
|---|---|
| Number of Conductors | 25 |
| Strands per Conductor | 7 |
| Conductor | Class B stranded copper, compressed or compact, per ASTM B3 and B8 |
| Diameter Over Conductor | 0.070 in (0.18 cm) |
| Insulation | Cross-linked polyethylene (XLPE) |
| Insulation Thickness | 30 mils (0.76 mm) |
| Conductor Colors | Black, numbered |
Grounding, Armor & Jacket
| Grounding Conductor | One 14 AWG uninsulated Class B stranded copper |
|---|---|
| Inner Jacket | Black polyvinyl chloride (PVC) |
| Inner Jacket Thickness | 85 mils (2.16 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.283 in (3.26 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 45 mils (1.14 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.373 in (3.49 cm) |
|---|---|
| Approximate Weight | 903 lbs/1000 ft (1344 kg/km) |
| Maximum Pull Tension | 822 lbs (372.85 kg) |
| Minimum Bend Radius | 9.6 in (24.38 cm) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Type Designation | Type TECK 90 |
| Maximum Continuous Operating Temperature | 90°C |
| Minimum Installation Temperature | -40°C |
| CSA Cold Bend and Impact Temperature | -40°C |
| Sunlight Resistant | Yes |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- CSA C22.2 No. 174
- CSA C22.2 No. 131 Type TECK 90 Cable
- CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
- CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
- CSA HL rating
- CSA SUN RES - for Sunlight Resistant rating
- CSA AG14 - Acid Gas Compliance
- IEEE 383 Flame Test (70,000 btu)
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
Southwire 56177804 Applications
- Exposed or concealed wiring in wet or dry locations.
- It may be run in ventilated, non-ventilated and ladder-type cable troughs and in ventilated flexible cableway, in wet, dry or classified locations.
- Control, lighting and power circuits in pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.