Southwire 56352201, Armored Cable 14 AWG 3C Copper 1 kV Black
Description
Southwire 56352201 is a 14 AWG three-conductor Teck 90 armored cable rated 1 kV, finished in a black PVC outer jacket over aluminum interlocked armor (AIA). Its 7-strand Class B copper conductors carry 45 mils of cross-linked polyethylene (XLPE) insulation identified red, black and blue, and are cabled with an uninsulated Class B stranded grounding conductor under a black PVC inner jacket. Standards include CSA C22.2 No. 131 Type TECK 90 Cable.
Southwire 56352201 Technical Specs
Conductors & Insulation
| Conductor Size | 14 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 7 |
| Conductor | Class B stranded copper, compressed, per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE) |
| Insulation Thickness | 45 mils (1.14 mm) |
| Conductor Identification | Red, black and blue |
Grounding, Armor & Jacket
| Grounding Conductor | Uninsulated Class B stranded grounding conductor |
|---|---|
| Inner Jacket | Black PVC |
| Armor | Aluminum interlocked armor (AIA) |
| Outer Jacket | Black PVC |
| Outer Jacket Thickness | 50 mils (1.27 mm) |
Dimensions & Weight
| Diameter Over Armor | 0.660 in (1.68 cm) |
|---|---|
| Approximate Outside Diameter | 0.760 in (1.93 cm) |
| Approximate Weight | 256 lbs/1000 ft (381 kg/km) |
| Copper Weight | 51 lbs/1000 ft (76 kg/km) |
| Minimum Bend Radius | 5.3 in (13.46 cm) |
Electrical
| DC Resistance at 25°C (ohms/1000 ft) | 2.631 |
|---|---|
| AC Resistance at 75°C (ohms/1000 ft) | 3.170 |
| Allowable Ampacity, Raceway, 75°C | 20 |
| Allowable Ampacity, Raceway, 90°C | 25 |
Ratings & Compliance
| Voltage Rating | 1 kV |
|---|---|
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 44 Thermoset-Insulated Wires and Cables; UL 1569 Metal-Clad Cables; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; CSA C22.2 No. 174; CSA C22.2 No. 131 Type TECK 90 Cable; CSA AG14 - Acid Gas Compliance; ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2; ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
Southwire 56352201 Applications
- Exposed or concealed wiring in wet or dry locations; the cable is sunlight resistant.
- Ventilated, non-ventilated and ladder-type cable troughs and ventilated flexible cableway, in wet, dry or classified locations, or direct burial.
- Typical circuits are control, lighting and power in pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.