Southwire 56680102, Metal Clad Cable 12 AWG 2C 2 Neutrals with Ground Stranded Copper THHN
Description
Southwire 56680102 is an Armorlite® Type MC neutral-per-phase cable with two 12 AWG 19-strand copper Type THHN/THWN phase conductors in black and red and two 12 AWG neutrals in white-black and white-red, plus a green insulated Type THHN/THWN ground conductor, under aluminum interlocked armor. Conductors rated 90°C dry as Type THHN/THWN. Unjacketed, for dry, indoor locations only.
Southwire 56680102 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Phase Conductors | 2 |
| Neutral Conductors | 2 x 12 AWG |
| Conductor | 19-strand class C compressed copper per ASTM B3 and B8 |
| Stranding | 19-strand |
| Conductor Colors | Black, Red (phases); White-Black, White-Red (neutrals); green (ground) |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.090 in (0.23 cm) |
Grounding and Armor
| Grounding | Green insulated polyvinyl chloride with nylon sheath Type THHN/THWN ground conductor |
|---|---|
| Ground Size | 1x12 |
| Binder | Mylar tape, with a print legend wrapped around the assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.568 in (1.44 cm) |
|---|---|
| Approximate Weight | 167 lbs per 1,000 ft (249 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry, Type THHN/THWN |
|---|---|
| Location | Dry, indoor locations only (unjacketed Type MC, NEC 330.10(A)(10)) |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 56680102 Applications
- Circuits affected by harmonics from non-linear switching loads such as computers, variable frequency drives, electrical test equipment and office equipment.
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fishing through or embedding in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
- Each neutral serves one circuit only (branch, multiwire branch or ungrounded feeder); see NEC 200.4 for the installation and marking of neutral conductors.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.