Southwire 56891899, Armored Cable 250 KCMIL 3C Copper 5 kV Orange
Description
Southwire 56891899 is a 250 kcmil three-conductor HVTECK medium voltage armored cable rated 5 kV at 100% insulation level, with an orange PVC outer jacket over aluminum interlocked armor (AIA). Each 37-strand Class B compressed bare copper conductor has a semi-conducting conductor shield, 90 mils of no-lead ethylene propylene rubber (NL-EPR) insulation, a strippable insulation shield and a helically wrapped 5 mil copper tape shield with 25% overlap. One 2 AWG bare copper grounding conductor, non-wicking fillers and a PVC inner jacket complete the core.
Southwire 56891899 Technical Specs
Conductors & Insulation
| Conductor Size | 250 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 90 mils (2.29 mm) |
| Insulation Level | 100% |
| Diameter Over Conductor | 0.558 in (1.42 cm) |
| Diameter Over Insulation | 0.768 in (1.95 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 0.828 in (2.10 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 2 AWG Class B compressed stranded bare copper |
|---|---|
| Filler | Non-hydroscoping, non-wicking fillers in the interstices |
| Binder | Polypropylene tape |
| Inner Jacket | PVC |
| Inner Jacket Thickness | 110 mils (2.79 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Outer Jacket | Orange polyvinyl chloride (PVC) |
| Outer Jacket Thickness | 75 mils (1.91 mm) |
Dimensions & Weight
| Diameter Over Armor | 2.402 in (6.10 cm) |
|---|---|
| Approximate Outside Diameter | 2.552 in (6.48 cm) |
| Approximate Weight | 4663 lbs/1000 ft (6939 kg/km) |
| Maximum Pull Tension | 6000 lbs (2721.55 kg) |
| Minimum Bend Radius | 17.9 in (45.47 cm) |
Ratings & Compliance
| Voltage Rating | 5 kV at 100% insulation level |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA T-29-520 Flame Test (210,000 BTU/Hr); IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test); AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 56891899 Applications
- The 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL.
- The line is sunlight and moisture resistant, exceptionally corona resistant, resistant to most chemical soils and acids, and flame retardant.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.