Southwire 57116001, Metal Clad Cable 10 AWG 4C with Ground Solid Copper THHN 600 V Dashed-Blue Armor
Description
Southwire 57116001 is a Duraclad® Type MC cable with four 10 AWG solid copper Type THHN/THWN conductors in black, white, red and blue, plus a green insulated Type THHN/THWN ground, under lightweight steel dashed-blue interlocked armor. The blue identifying the cable is the armor's dashed-blue marking. Rated 600 V; conductors rated 90°C dry as Type THHN/THWN.
Southwire 57116001 Technical Specs
Conductors and Insulation
| Conductor Size | 10 AWG |
|---|---|
| Number of Conductors | 4, plus one grounding conductor |
| Conductor | Solid copper |
| Stranding | Solid |
| Conductor Colors | Black, White, Red, Blue; green (ground) |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 25 mils (0.64 mm) |
| Diameter Over Conductor | 0.101 in (0.26 cm) |
Grounding and Armor
| Grounding | Green insulated polyvinyl chloride with nylon sheath Type THHN/THWN ground |
|---|---|
| Ground Size | 1x10 |
| Binder | Mylar tape, with a print legend wrapped around the assembly |
| Armor | Lightweight steel dashed-blue interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.633 in (1.61 cm) |
|---|---|
| Approximate Weight | 296 lbs per 1,000 ft (440 kg/km) |
Ratings
| Voltage Rating | 600 V |
|---|---|
| Conductor Temperature Rating | 90°C dry, Type THHN/THWN |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 57116001 Applications
- Branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fishing through or embedding in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.