Description
Southwire 57383599 is a 6 AWG stranded aluminum building wire in blue, from the SIMpull line and carrying the THHN, THWN-2 and AWM designations. Its 7-strand compact stranded aluminum conductor is insulated with heat and moisture resistant PVC under a nylon jacket utilizing SIMpull Technology, and The voltage is 600 volts for all applications.
Southwire 57383599 Technical Specs
Construction
| Conductor Size | 6 AWG |
|---|---|
| Conductor Material | Class B compact stranded bare aluminum per ASTM B800 and ASTM B801, or Single Input Wire (SIW) compact aluminum per ASTM B836 |
| Number of Strands | 7 |
| Insulation | Heat and moisture resistant PVC |
| Nylon Jacket | Nylon, utilizing SIMpull Technology |
| Type Designation | THHN-THWN-2 AWM |
| Insulation Colour | Blue |
Dimensions and Weight
| Diameter Over Conductor | 0.169 in (0.43 cm) |
|---|---|
| Insulation Thickness | 30 mils (0.76 mm) |
| Nylon Jacket Thickness | 6 mils (0.15 mm) |
| Approx. Overall Diameter | 0.243 in (0.62 cm) |
| Aluminum Content Weight | 24 lbs/1000 ft (36 kg/km) |
| Approx. Total Weight | 39 lbs/1000 ft (58 kg/km) |
Ratings
| Voltage | 600 volts, all applications |
|---|---|
| THHN | Dry locations, not to exceed 90°C |
| THWN-2 | Wet or dry locations, not to exceed 90°C; not to exceed 75°C when exposed to oil |
Features
| Oil and Gasoline | Oil and Gasoline Resistant II |
|---|---|
| Flame Tests | VW-1, all sizes; FT1, all sizes |
| Construction | NEMA WC-70 construction requirements |
| RoHS | Compliant |
Standards
| ASTM B800 | 8000 Series Aluminum Alloy Wire |
|---|---|
| ASTM B801 | Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy |
| ASTM B836 | Compact Rounded Stranded Aluminum Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| Federal Specification | A-A-59544 |
Southwire 57383599 Applications
- Pulled into conduit for services, feeders and branch circuits in commercial or industrial applications, as specified in the National Electrical Code and other applicable codes and standards.
- Installs without a pulling lubricant.