Southwire 57598889, Armored Cable 750 KCMIL 3C Aluminum 15 kV Black
Southwire · MPN 57598889
Description
Southwire 57598889 is a 750 kcmil three-conductor medium voltage armored cable rated 15 kV at 133% insulation level, with a black PVC outer jacket over aluminum interlocked armor (AIA). Its 53-strand Class B compact 8000 Series aluminum conductors each carry a semi-conducting conductor shield, 220 mils of no-lead ethylene propylene rubber (NL-EPR) insulation, a strippable insulation shield and a helically wrapped 5 mil copper tape shield with 25% overlap. Three separate 1 AWG bare copper ground wires, together sized at 50% of the phase conductor's circular mil area, are cabled with the phases.
Southwire 57598889 Technical Specs
Conductors & Insulation
| Conductor Size | 750 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 53 |
| Conductor | Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836 |
| Conductor Separator | Used (500 kcmil and larger) |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 220 mils (5.59 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.908 in (2.31 cm) |
| Diameter Over Insulation | 1.426 in (3.62 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 1.486 in (3.77 cm) |
Grounding, Armor & Jacket
| Grounding Conductors | Three 1 AWG Class B compressed stranded bare copper, combined 50% of phase conductor circular mils |
|---|---|
| Filler | As needed to round the core |
| Binder | Polypropylene tape |
| Armor | Aluminum interlocked armor (AIA) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Outer Jacket Thickness | 90 mils (2.29 mm) |
Dimensions & Weight
| Diameter Over Armor | 3.581 in (9.10 cm) |
|---|---|
| Approximate Outside Diameter | 3.769 in (9.57 cm) |
| Approximate Weight | 6672 lbs/1000 ft (9929 kg/km) |
| Maximum Pull Tension | 13500 lbs (6123.49 kg) |
| Minimum Bend Radius | 26.3 in (66.80 cm) |
Ratings & Compliance
| Voltage Rating | 15 kV at 133% insulation level |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Location Rating | Class I and II, Division 2, per NEC Articles 501 and 502 |
| Silicone | Silicone free |
| Standards | ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy; ASTM B836 Compact Rounded Stranded Aluminum Conductors; UL 1072 Medium-Voltage Power Cables; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE); ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Domestic Content | Made in America: compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 57598889 Applications
- Wet and dry areas, conduits, ducts, troughs, trays and direct burial.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.