Southwire 57622089, Armored Cable 750 KCMIL 3C Aluminum XHHW-2 600 V
Southwire · MPN 57622089
Description
Southwire 57622089 is a 750 KCMIL three-conductor armored power cable rated 600 V. Its three 58-strand 8000 Series aluminum conductors carry 80 mils of XHHW-2 XLPE, and three separate 2/0 AWG bare aluminum ground wires, sized together to 50% of the phase conductor, run with them. Aluminum interlocked armor (AIA) and a PVC outer jacket complete the cable.
Southwire 57622089 Technical Specs
Conductors & Insulation
| Conductor Size | 750 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 58 |
| Conductor | Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Insulation Thickness | 80 mils (2.03 mm) |
| Diameter Over Conductor | 0.908 in (2.31 cm) |
Grounding, Armor & Jacket
| Grounding Conductors | Three separate 2/0 AWG Class B compact stranded 8000 Series aluminum ground wires, with a combined circular mil of 50% of the phase conductor |
|---|---|
| Filler | Paper or polypropylene |
| Binder | Polypropylene tape |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 2.624 in (6.66 cm) |
| Outer Jacket | Polyvinyl chloride (PVC) |
| Jacket Thickness | 80 mils (2.03 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.790 in (7.09 cm) |
|---|---|
| Approximate Weight | 4071 lbs/1000 ft (6058 kg/km) |
| Maximum Pull Tension | 13500 lbs (6123.49 kg) |
| Minimum Bend Radius | 19.5 in (49.53 cm) |
Ratings & Compliance
| Voltage Rating | 600 V |
|---|---|
| Operating Temperatures | 90°C normal operation (wet and dry locations); 130°C emergency overload; 250°C short circuit |
| Location Rating | Class I, II, and III, Division 2 per NEC Article 501 and 502 |
| Silicone Free | Yes |
| Standards | ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy; ASTM B836 Compact Rounded Stranded Aluminum Conductors; UL 44 Thermoset-Insulated Wires and Cables; UL 1569 Metal-Clad Cables; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
Southwire 57622089 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial and aerial runs supported by a messenger.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.