Southwire 58092999, Metal Clad Cable 500 kcmil 3C with Ground Stranded Copper THHN Black Jacket
Description
Southwire 58092999 is an Armorlite® Type MC feeder cable with three 500 kcmil 37-strand copper THHN/THWN conductors (brown, orange and yellow), plus a 1/0 AWG green insulated copper ground, under aluminum interlocked armor and a black jacket. Conductors are rated 90°C dry.
Southwire 58092999 Technical Specs
Conductors and Insulation
| Conductor Size | 500 kcmil |
|---|---|
| Number of Conductors | 3, plus a grounding conductor |
| Conductor | Class B compressed copper per ASTM B3 and ASTM B8 |
| Stranding | 37-strand |
| Conductor Colors | Brown, Orange, Yellow |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 70 mils (1.78 mm) |
| Diameter Over Conductor | 0.789 in (2.00 cm) |
Grounding and Armor
| Grounding Conductor | Green insulated copper ground, 1/0 AWG |
|---|---|
| Ground Size | 1x1/0 |
| Filler | Fillers as needed |
| Binder | Mylar tape with print legend, wrapped around the assembly |
| Armor | Aluminum interlocked armor |
| Jacket | Black |
| Jacket Thickness | 75 mils (1.91 mm) |
Dimensions and Weight
| Diameter Over Armor | 2.275 in (5.78 cm) |
|---|---|
| Approximate Outside Diameter | 2.433 in (6.18 cm) |
| Approximate Weight | 6095 lbs per 1,000 ft (9070 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry (Type THHN/THWN) |
|---|---|
| Anti-Short Bushing | Not required |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 58092999 Applications
- Feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(E).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.