Southwire 58232501, Metal Clad Cable 12 AWG 2C with Ground Solid Copper THHN Green Steel Armor
Description
Southwire 58232501 is an MC-AP™ HCF health care facility Type MC cable with two 12 AWG solid copper THHN/THWN conductors (black and white), a green insulated ground and a bare 8000 series aluminum grounding/bonding conductor under green galvanized steel interlocked armor. The conductors are rated 90°C dry.
Southwire 58232501 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 2, plus a grounding conductor |
| Conductor | Solid copper per ASTM B3 |
| Stranding | Solid |
| Conductor Colors | Black, White |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
Grounding and Armor
| Grounding | Solid or stranded copper green insulated ground, polyvinyl chloride with nylon sheath Type THHN/THWN, with redundant grounding by a solid bare 8000 series aluminum grounding/bonding conductor and the armor |
|---|---|
| Ground Size | 1x12 |
| Armor Grounding | Armor in contact with the aluminum grounding/bonding conductor serves as a redundant equipment grounding path component |
| Binder | Mylar tape |
| Armor | Green galvanized steel interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.512 in (1.30 cm) |
|---|---|
| Approximate Weight | 188 lbs per 1,000 ft (280 kg/km) |
Ratings
| Conductor Temperature | 90°C dry (Type THHN/THWN) |
|---|
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 58232501 Applications
- Branch-circuit wiring for patient care areas of hospitals, medical centers and other health care facilities, including nursing homes, dental offices, clinics and outpatient facilities, when installed per NEC Articles 517 and 330 and mechanically protected per Article 300.4. Use in classified anesthetizing areas is prohibited.
- Applications requiring redundant, dedicated or isolated grounding paths.
- Fished or embedded in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
- Use with UL Listed MCI-A fittings.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.