Southwire 58404299, Medium Voltage Cable 3/0 AWG 3C Copper 15 kV Black
Description
Southwire 58404299 is a shielded medium voltage power cable, rated 15 kV at the 133% insulation level, with three 3/0 AWG copper phase conductors and one 3 AWG bare copper ground. Each phase carries 220 mils of NL-EPR insulation under a helically wrapped 5 mil copper tape shield, and wax paper filler and a poly glass tape binder sit beneath an overall black CPE-TP jacket.
Southwire 58404299 Technical Specs
Conductor & Insulation
| Conductor Size (per conductor) | 3/0 AWG |
|---|---|
| Number of Conductors | 3 plus ground |
| Strands (per conductor) | 19 |
| Conductor | Class B compressed stranded bare copper, ASTM B3 and ASTM B8 |
| Diameter Over Conductor (per conductor) | 0.456 in (1.16 cm) |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness (per conductor) | 220 mils (5.59 mm) |
| Diameter Over Insulation (per conductor) | 0.934 in (2.37 cm) |
Shield, Ground & Jacket
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield (per conductor) | 0.994 in (2.52 cm) |
| Grounding Conductor | One 3 AWG Class B compressed stranded bare copper |
| Filler and Binder | Wax paper filler; poly glass tape binder |
| Jacket | Black thermoplastic chlorinated polyethylene (CPE-TP) |
| Jacket Thickness | 110 mils (2.79 mm) |
Dimensions & Weight
| Approximate Outside Diameter (cable) | 2.418 in (6.14 cm) |
|---|---|
| Approximate Weight | 3,738 lbs/1000 ft (5,563 kg/km) |
| Maximum Pull Tension | 4,027 lbs (1826.61 kg) |
| Minimum Bend Radius | 16.9 in (42.93 cm) |
Ratings & Standards
| Voltage Rating | 15 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend Rating | -35°C |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire; UL 1072 Medium-Voltage Power Cables; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Domestic Content | Compliant with Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 58404299 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and trays.
- Direct burial.
- Class I and II, Division 2 per NEC Article 501 and 502.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.