Southwire 58425899, Armored Cable 1000 KCMIL 1C Copper 1 kV Black
Southwire · MPN 58425899
Description
Southwire 58425899 is a 1000 KCMIL single-conductor Type TECK 90 armored power cable rated 1 kV. Its 61-strand compressed copper conductor carries 90 mils of XLPE, and a concentric serve of bare copper bonding conductors surrounds it. A black PVC inner jacket, aluminum interlocked armor (AIA) and a black PVC outer jacket complete the cable. This line is a CSA approved armoured cable for industrial and commercial applications.
Southwire 58425899 Technical Specs
Conductors & Insulation
| Conductor Size | 1000 KCMIL |
|---|---|
| Number of Conductors | 1 |
| Strands per Conductor | 61 |
| Conductor | Class B stranded compressed copper per ASTM B3 and ASTM B8 |
| Insulation | Cross-linked polyethylene (XLPE), 90°C |
| Insulation Thickness | 90 mils (2.29 mm) |
| Diameter Over Conductor | 1.117 in (2.84 cm) |
Grounding, Armor & Jacket
| Concentric Bonding Conductors | Class B concentric bare copper wire serve |
|---|---|
| Binder | Polypropylene separator |
| Inner Jacket | Black polyvinyl chloride (PVC) |
| Inner Jacket Thickness | 60 mils (1.52 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.935 in (4.91 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 55 mils (1.40 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.045 in (5.19 cm) |
|---|---|
| Approximate Weight | 4480 lbs/1000 ft (6667 kg/km) |
| Maximum Pull Tension | 8000 lbs (3628.74 kg) |
| Minimum Bend Radius | 14.3 in (36.32 cm) |
Ratings & Compliance
| Voltage Rating | 1 kV |
|---|---|
| Type Designation | Type TECK 90 |
| Temperatures | 90°C maximum continuous operating; 140°C emergency overload; -25°C minimum installation; -40°C CSA cold bend and impact |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 131 Type TECK 90 Cable; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; CSA AG14 - Acid Gas Compliance; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test) |
Southwire 58425899 Applications
- Cable trays, duct banks, troughs and continuous rigid cable supports, along with direct burial and classified locations.
- Concrete encasement is permitted.
- The line is rated FT4, -40°C, HL, AG14 and 90°C for use in harsh Canadian environments.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.