Southwire 58557402, Metal Clad Cable 10 AWG 2C with Ground Solid Copper THHN
Description
Southwire 58557402 is an MC-AP™ all purpose Type MC cable with two 10 AWG solid copper THHN/THWN conductors (brown and yellow) and a full-sized bare 8000 series aluminum grounding/bonding conductor under aluminum interlocked armor. The armor and the bare aluminum conductor form the equipment ground path, and the conductors are rated 90°C dry.
Southwire 58557402 Technical Specs
Conductors and Insulation
| Conductor Size | 10 AWG |
|---|---|
| Number of Conductors | 2, plus a grounding conductor |
| Conductor | Solid copper per ASTM B3 |
| Stranding | Solid |
| Conductor Colors | Brown, Yellow |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 25 mils (0.64 mm) |
| Diameter Over Conductor | 0.101 in (0.26 cm) |
Grounding and Armor
| Grounding | Full-sized bare 8000 series aluminum grounding/bonding conductor; the armor and the bare aluminum conductor form the equipment ground path |
|---|---|
| Binder | Mylar tape |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.555 in (1.41 cm) |
|---|---|
| Approximate Weight | 130 lbs per 1,000 ft (193 kg/km) |
Ratings
| Conductor Temperature | 90°C dry (Type THHN/THWN) |
|---|
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 58557402 Applications
- Branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.