Southwire 58640599, Armored Cable 350 KCMIL 1C Copper 1 kV Black
Description
Southwire 58640599 is a 350 KCMIL single-conductor Type TECK 90 armored power cable rated 1 kV. Its 37-strand compressed copper conductor carries 90 mils of XLPE, and a serve of 13 x 12 AWG concentric bare copper bonding wires surrounds it. A black PVC inner jacket, aluminum interlocked armor (AIA) and a black PVC outer jacket complete the cable. This line is a CSA approved armoured cable for industrial and commercial applications.
Southwire 58640599 Technical Specs
Conductors & Insulation
| Conductor Size | 350 KCMIL |
|---|---|
| Number of Conductors | 1 |
| Strands per Conductor | 37 |
| Conductor | Class B stranded compressed copper per ASTM B3 and ASTM B8 |
| Insulation | Cross-linked polyethylene (XLPE), 90°C |
| Insulation Thickness | 90 mils (2.29 mm) |
| Diameter Over Conductor | 0.661 in (1.68 cm) |
Grounding, Armor & Jacket
| Concentric Bonding Conductors | Class B concentric bare copper wire serve, 13 x 12 AWG |
|---|---|
| Binder | Polypropylene separator |
| Inner Jacket | Black polyvinyl chloride (PVC) |
| Inner Jacket Thickness | 60 mils (1.52 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.449 in (3.68 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 45 mils (1.14 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.539 in (3.91 cm) |
|---|---|
| Approximate Weight | 1935 lbs/1000 ft (2880 kg/km) |
| Maximum Pull Tension | 2800 lbs (1270.06 kg) |
| Minimum Bend Radius | 10.7 in (27.18 cm) |
Ratings & Compliance
| Voltage Rating | 1 kV |
|---|---|
| Type Designation | Type TECK 90 |
| Temperatures | 90°C maximum continuous operating; 140°C emergency overload; -25°C minimum installation; -40°C CSA cold bend and impact |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 131 Type TECK 90 Cable; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; CSA AG14 - Acid Gas Compliance; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test) |
Southwire 58640599 Applications
- Cable trays, duct banks, troughs and continuous rigid cable supports, along with direct burial.
- Classified locations are among the installations the line is rated for.
- Concrete encasement is permitted.
- The line has CSA AG14 acid gas compliance and is rated for use in harsh Canadian environments.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.