Southwire 58692502, Medium Voltage Cable 1/0 AWG 1C Aluminum 25 kV 100% TRXLP 16x14CN Super Smooth
Description
Southwire 58692502 is a 25 kV single-conductor medium voltage cable in the 25kV HI-DRI Primary UD TRXLP Cable line, built on a 1/0 AWG, 19-strand moisture blocked unilay compressed stranded 1350-H16/26 aluminum phase conductor. Its tree-retardant cross-linked polyethylene (TRXLP) primary insulation is 260 mils thick at a 100% insulation level, between semi-conducting strand and insulation shields, with a Super Smooth conductor shield. A concentric neutral of bare copper wires (16x14CN) lies under a sunlight resistant, -40°C rated, insulating linear low density polyethylene jacket.
Southwire 58692502 Technical Specs
Conductor
| Conductor Size | 1/0 AWG |
|---|---|
| Number of Conductors | 1 |
| Strands | 19 |
| Conductor | Moisture blocked unilay compressed stranded 1350-H16/26 aluminum |
| Strand Shield | Semi-conducting cross-linked polyethylene; Super Smooth conductor shield |
Insulation and Shielding
| Insulation | Tree-retardant cross-linked polyethylene (TRXLP) |
|---|---|
| Insulation Thickness | 260 mils (6.60 mm) |
| Insulation Level | 100% |
| Insulation Shield | Semi-conducting cross-linked polyethylene |
Neutral and Jacket
| Concentric Neutral | Bare copper wires, 16x14CN |
|---|---|
| Jacket | Insulating linear low density polyethylene; sunlight resistant, -40°C rated |
| Jacket Marking | Surface print, with the lightning bolt symbol for supply cables indented |
Dimensions and Weight
| Nominal Outside Diameter | 1,220 mils (30.99 mm) |
|---|---|
| Nominal Total Weight | 743 lbs/1000 ft (1,105 kg/km) |
Ratings
| Voltage | 25 kV; for use at 25,000 volts or less |
|---|---|
| Conductor Temperature | Not to exceed 90°C, normal operation |
Standards
The 25kV HI-DRI Primary UD TRXLP Cable meets or exceeds the following specifications.
| ASTM B231 | Aluminum 1350 Conductors, Concentric-Lay-Stranded |
|---|---|
| ASTM B609 | Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes |
| ASTM B3 | Soft Annealed Copper Wire |
| Other Documents | ICEA S-94-649, AEIC CS-8, RUS U-1 |
Southwire 58692502 Applications
- Primary underground distribution in conduit systems.
- Wet or dry locations, direct burial and underground duct, including installations exposed to sunlight.