Southwire 58768599, Armored Cable 750 KCMIL 1C Copper 15 kV Red
Southwire · MPN 58768599
Description
Southwire 58768599 is a 750 KCMIL single-conductor HVTECK armored cable rated 15 kV, 133% insulation level. Its 61-strand compressed bare copper conductor is insulated with 220 mils of NL-EPR between semi-conducting conductor and insulation shields, with 21 x 12 AWG concentric copper bond/shield wires over the insulation. A PVC inner jacket, aluminum interlocked armor (AIA) and a red PVC outer jacket complete the cable. The 15kV HVTECK line is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL.
Southwire 58768599 Technical Specs
Conductors & Insulation
| Conductor Size | 750 KCMIL |
|---|---|
| Number of Conductors | 1 |
| Strands per Conductor | 61 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 220 mils (5.59 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.968 in (2.46 cm) |
| Diameter Over Insulation | 1.464 in (3.72 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Concentric Shield | 21 x 12 AWG concentrically applied copper bond/shield wires |
| Separator | Mylar tape |
| Diameter Over Shield | 1.524 in (3.87 cm) |
Grounding, Armor & Jacket
| Inner Jacket | PVC |
|---|---|
| Inner Jacket Thickness | 110 mils (2.79 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 2.276 in (5.78 cm) |
| Outer Jacket | Red polyvinyl chloride (PVC) |
| Jacket Thickness | 75 mils (1.91 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.426 in (6.16 cm) |
|---|---|
| Approximate Weight | 4617 lbs/1000 ft (6871 kg/km) |
| Maximum Pull Tension | 6000 lbs (2721.55 kg) |
| Minimum Bend Radius | 29.1 in (73.91 cm) |
Ratings & Compliance
| Voltage Rating | 15 kV |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA T-29-520 Flame Test (210,000 BTU/Hr); IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger); FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test); AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 58768599 Applications
- Industrial and commercial medium voltage installations.
- The line is sunlight and moisture resistant, flame retardant, exceptionally corona resistant and resistant to most chemical soils and acids.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.