Southwire 59199199, Power Tray Cable 1/0 AWG 3C Tinned Copper XHHW-2 TC-ER 1000V Black
Description
Southwire 59199199 is a 1/0 AWG, 3-conductor power tray cable with tinned copper conductors, ethylene propylene rubber (EPR) Type XHHW-2 insulation and a black thermoplastic chlorinated polyethylene (CPE-TP) jacket. It is Type TC-ER and rated 1000V. A 6 AWG tinned copper grounding conductor is included in addition to the 3 circuit conductors.
Southwire 59199199 Technical Specs
Construction
| Conductor Size | 1/0 AWG |
|---|---|
| Number of Conductors | 3 |
| Conductor | Class B compressed stranded tinned copper per ASTM B8 and B33 |
| Strands per Conductor | 19 |
| Insulation | Ethylene propylene rubber (EPR), Type XHHW-2 |
| Conductor Identification | Numbered conductors: 1-ONE, 2-TWO, 3-THREE |
| Grounding Conductor | One 6 AWG Class B compressed stranded tinned copper, in addition to the 3 circuit conductors |
| Jacket | Thermoplastic chlorinated polyethylene (CPE-TP) |
| Jacket Colour | Black |
| Type Designation | TC-ER |
Dimensions and Weight
| Diameter Over Conductor | 0.361 in (0.92 cm) |
|---|---|
| Insulation Thickness | 55 mils (1.40 mm) |
| Jacket Thickness | 80 mils (2.03 mm) |
| Approx. Overall Diameter | 1.216 in (3.09 cm) |
| Copper Weight | 1069 lbs/1000 ft (1591 kg/km) |
| Approx. Weight | 1406 lbs/1000 ft (2092 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 1000V |
|---|---|
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Other Ratings | Sunlight resistant; silicone free |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| ASTM B33 | Standard Specification for Tin-Coated Soft or Annealed Copper Wire |
| UL 44 | Thermoset-Insulated Wires and Cables |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 4 |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 59199199 Applications
- Wet and dry areas, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial runs supported by a messenger.
- Exposed runs (TC-ER) per NEC 336.10.
- Class I, II and III, Division 2 per NEC Article 501 and 502.