Southwire 59638599, Armored Cable 4/0 AWG 3C Copper 35 kV Orange
Southwire · MPN 59638599
Description
Southwire 59638599 is a 4/0 AWG three-conductor shielded medium-voltage armored cable rated 35 kV, 133% insulation level. Its three 19-strand compressed bare copper conductors carry 420 mils of NL-EPR with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and one 3 AWG bare copper grounding conductor runs with them. ARMOR-X® continuous corrugated welded armor and an orange PVC outer jacket complete the cable. Part of the 35KV ARMOR-X armored cable line, for wet and dry areas.
Southwire 59638599 Technical Specs
Conductors & Insulation
| Conductor Size | 4/0 AWG |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 19 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 420 mils (10.67 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.512 in (1.30 cm) |
| Diameter Over Insulation | 1.376 in (3.50 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 1.436 in (3.65 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 3 AWG Class B compressed stranded bare copper grounding conductor |
|---|---|
| Filler | Wax paper |
| Binder | Polypropylene tape |
| Armor | ARMOR-X® continuous corrugated welded armor |
| Diameter Over Armor | 3.850 in (9.78 cm) |
| Outer Jacket | Orange polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 4.020 in (10.21 cm) |
|---|---|
| Approximate Weight | 7164 lbs/1000 ft (10661 kg/km) |
| Maximum Pull Tension | 5078 lbs (2303.34 kg) |
| Minimum Bend Radius | 28.1 in (71.37 cm) |
Ratings & Compliance
| Voltage Rating | 35 kV |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -50°C |
| Location Rating | Class I, II, and III, Division 1 and 2 per NEC Article 501, 502, and 503 |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; UL 1072 Medium-Voltage Power Cables; UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 59638599 Applications
- Wet and dry areas, conduits, ducts, troughs and trays, along with direct burial.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.