Southwire 59766301, Metal Clad Cable 12 AWG 2C with Ground Solid Copper THHN plus 16 AWG Signal Pair
Description
Southwire 59766301 is an MC-PCS HCF Duo™ Type MC cable for health care facilities, with a power element and a signal element under aluminum interlocked armor. The power element is two 12 AWG solid copper THHN/THWN conductors, yellow and gray, with a green insulated ground and a 10 AWG solid bare aluminum grounding/bonding conductor; the armor and the bare aluminum conductor form the equipment ground path. The signal element is a pair of 16 AWG solid copper Type TFN singles, pink and purple, under their own light blue jacket. Conductors are rated 90°C dry, for dry, indoor locations.
Southwire 59766301 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Power Conductors | 2, plus a grounding conductor |
| Conductor | Solid copper per ASTM B3 |
| Conductor Colors | Yellow, Gray |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
| Signal Pair | Two 16 AWG solid copper Type TFN insulated singles, pink and purple, under an overall light blue jacket |
Grounding and Armor
| Ground | Green polyvinyl chloride with nylon sheath Type THHN/THWN insulated ground conductor |
|---|---|
| Redundant Ground | 10 AWG solid, full-sized bare 8000 series aluminum grounding/bonding conductor per ASTM B800; armor and bare aluminum conductor form the equipment ground path |
| Binder | Mylar tape; binder tape with print legend wrapped around the assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.632 in (1.61 cm) |
|---|---|
| Approximate Weight | 164 lbs per 1,000 ft (244 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry (Type THHN/THWN) |
|---|---|
| Location | Dry, indoor locations only per NEC 330.10(A)(10) (unjacketed) |
Standards and Compliance
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B800 (aluminum grounding/bonding conductor) | 8000 Series Aluminum Alloy Wire |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American requirements, 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 59766301 Applications
- Branch-circuit wiring for patient care areas of hospitals, medical centers and other health care facilities, including nursing homes, dental offices, clinics and outpatient facilities, when installed in accordance with NEC Articles 517 and 330 and mechanically protected per Article 300.4.
- Not for use in classified anesthetizing areas.
- Circuits requiring redundant, dedicated or isolated grounding paths.
- Power, lighting, control and signal circuits.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5.
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
- Termination with UL Listed MCI-A fittings.