Description
Southwire 59778799 is a single-conductor shielded medium voltage power cable, rated 35 kV at the 133% insulation level. Its 1000 KCMIL 58-strand compact aluminum conductor carries 420 mils of NL-EPR insulation under a helically wrapped 5 mil copper tape shield, finished with a black SIMpull PVC jacket.
Southwire 59778799 Technical Specs
Conductor & Insulation
| Conductor Size | 1000 KCMIL |
|---|---|
| Number of Conductors | 1 |
| Strands | 58 |
| Conductor | Class B compact stranded 8000 Series aluminum, ASTM B800 and ASTM B836 |
| Diameter Over Conductor | 1.060 in (2.69 cm) |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 420 mils (10.67 mm) |
| Diameter Over Insulation | 1.968 in (5.00 cm) |
Shield & Jacket
| Conductor Shield | Semi-conducting cross-linked copolymer, with a conductor separator |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 2.028 in (5.15 cm) |
| Jacket | Black SIMpull polyvinyl chloride (PVC) |
| Jacket Thickness | 110 mils (2.79 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.278 in (5.79 cm) |
|---|---|
| Approximate Weight | 2,722 lbs/1000 ft (4,051 kg/km) |
| Maximum Pull Tension | 6,000 lbs (2721.55 kg) |
| Minimum Bend Radius | 27.3 in (69.34 cm) |
Ratings & Standards
| Voltage Rating | 35 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend Rating | -25°C cold bend and cold impact; LTDD marking |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Jacket Friction | SIM technology PVC, coefficient of friction 0.2; installs in conduit without lubrication |
| Standards | ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy; ASTM B836 Compact Rounded Stranded Aluminum Conductors; UL 1072 Medium-Voltage Power Cables; UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger); CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger); CSA C22.2 No. 2556 / UL 2556 Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV; IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger); AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Domestic Content | Compliant with Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 59778799 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and trays.
- Direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5).
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.