Southwire 59945999, Control Tray Cable 14 AWG 5C Tinned Copper XHHW-2 TC-ER 1000V Black
Description
Southwire 59945999 is a 14 AWG 5-conductor control tray cable with tinned copper conductors, ethylene propylene rubber (EPR) Type XHHW-2 insulation and a black thermoplastic chlorinated polyethylene (CPE-TP) jacket. It is Type TC-ER and rated 1000V.
Southwire 59945999 Technical Specs
Construction
| Conductor Size | 14 AWG |
|---|---|
| Number of Conductors | 5 |
| Conductor | 7-strand Class B compressed tinned copper per ASTM B33 and B8 |
| Strands per Conductor | 7 |
| Insulation | Ethylene propylene rubber (EPR), Type XHHW-2 |
| Conductor Identification | Black, White, Red, Green, Orange (ICEA S-58-679 Method 1, Table 1) |
| Jacket | Thermoplastic chlorinated polyethylene (CPE-TP) |
| Jacket Colour | Black |
| Type Designation | TC-ER |
Dimensions and Weight
| Insulation Thickness | 30 mils (0.76 mm) |
|---|---|
| Jacket Thickness | 45 mils (1.14 mm) |
| Approx. Overall Diameter | 0.461 in (1.17 cm) |
| Minimum Bend Radius | 1.8 in (4.57 cm) |
| Copper Weight | 62 lbs/1000 ft (92 kg/km) |
| Approx. Total Weight | 129 lbs/1000 ft (192 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 1000V |
|---|---|
| Conductor Temperature | 90°C wet and dry; 130°C emergency overload; 250°C short circuit |
| Environmental | Sunlight resistant; oil resistant; silicone free |
| DC Resistance at 25°C | 2.631 ohms/1000 ft |
| AC Resistance at 75°C | 3.170 ohms/1000 ft |
| Allowable Ampacity, Raceway, 75°C | 16 A |
| Allowable Ampacity, Raceway, 90°C | 20 A |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| ASTM B33 | Tin-Coated Soft or Annealed Copper Wire |
| UL 44 | Thermoset-Insulated Wires and Cables |
| UL 44 VW-1 | Vertical flame test on individual conductors |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 1 Table 1 |
| ICEA S-73-532 | Control, Thermocouple Extension and Instrumentation Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 59945999 Applications
- Wet and dry areas, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial runs supported by a messenger.
- Class I, II and III, Division 2 per NEC Article 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.