Description
Southwire 59961999 is a 3/0 AWG 3-conductor power tray cable with Class B compact stranded 8000 Series aluminum alloy conductors, cross-linked polyethylene (XLPE) Type XHHW-2 insulation and a black sunlight-resistant PVC jacket. It is Type TC-ER and rated 1000V. A bare 4 AWG aluminum alloy grounding conductor is included in addition to the three circuit conductors.
Southwire 59961999 Technical Specs
Construction
| Conductor Size | 3/0 AWG |
|---|---|
| Number of Conductors | 3 |
| Conductor | Class B compact stranded 8000 Series aluminum alloy per ASTM B800 and ASTM B836 |
| Strands per Conductor | 15 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Conductor Identification | 1-Black, 2-Red, 3-Blue (ICEA S-58-679 Method 3) |
| Grounding Conductor | One 4 AWG bare grounding conductor, Class B compact stranded 8000 Series aluminum alloy |
| Filler and Binder | Paper filler; polyester flat thread binder tape |
| Jacket | Sunlight-resistant polyvinyl chloride (PVC) |
| Jacket Colour | Black |
| Type Designation | TC-ER |
Dimensions and Weight
| Diameter Over Conductor | 0.422 in (1.07 cm) |
|---|---|
| Insulation Thickness | 55 mils (1.40 mm) |
| Jacket Thickness | 80 mils (2.03 mm) |
| Approx. Overall Diameter | 1.324 in (3.36 cm) |
| Aluminum Weight | 518 lbs/1000 ft (771 kg/km) |
| Approx. Total Weight | 918 lbs/1000 ft (1366 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 1000V |
|---|---|
| Conductor Temperature | 90°C wet and dry; 130°C emergency overload; 250°C short circuit |
| Environmental | Silicone free |
Standards
| ASTM B800 | 8000 Series Aluminum Alloy Wire |
|---|---|
| ASTM B836 | Compact Rounded Stranded Aluminum Conductors |
| UL 44 | Thermoset-Insulated Wires and Cables |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE) |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 59961999 Applications
- Wet and dry areas, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial runs supported by a messenger.
- Class I, II and III, Division 2 per NEC Article 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.