Southwire 60039599, Medium Voltage Cable 4/0 AWG 3C Copper 2400 V
Description
Southwire 60039599 is a 2400 V non-shielded medium voltage power cable with three 4/0 AWG copper conductors and one 3 AWG bare copper ground. Each conductor carries a semi-conducting conductor shield and 90 mils of NL-EPR insulation; wax paper filler, a poly glass tape binder and an overall PVC jacket complete the cable, rated 105°C continuous.
Southwire 60039599 Technical Specs
Conductor & Insulation
| Conductor Size (per conductor) | 4/0 AWG |
|---|---|
| Number of Conductors | 3 plus ground |
| Strands (per conductor) | 19 |
| Conductor | Class B compressed stranded bare copper, ASTM B3 and ASTM B8 |
| Diameter Over Conductor (per conductor) | 0.512 in (1.30 cm) |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness (per conductor) | 90 mils (2.29 mm) |
| Diameter Over Insulation (per conductor) | 0.715 in (1.82 cm) |
Shield, Ground & Jacket
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Shielding | Non-shielded |
| Grounding Conductor | One 3 AWG Class B compressed stranded bare copper |
| Filler and Binder | Wax paper filler; poly glass tape binder |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Thickness | 110 mils (2.79 mm) |
Dimensions & Weight
| Approximate Outside Diameter (cable) | 1.774 in (4.51 cm) |
|---|---|
| Approximate Weight | 2,997 lbs/1000 ft (4,460 kg/km) |
| Maximum Pull Tension | 5,078 lbs (2303.34 kg) |
| Minimum Bend Radius | 12.4 in (31.50 cm) |
Ratings & Standards
| Voltage Rating | 2400 V |
|---|---|
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire; UL 1072 Medium-Voltage Power Cables; UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test; ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables |
| Domestic Content | Compliant with Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 60039599 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and trays.
- Direct burial.
- Class I and II, Division 2 per NEC Article 501 and 502.