Southwire 60751302, Substation Cable 12 AWG 4C Copper FR-XLPE Thermoset CPE Jacket 600 V Black
Description
Southwire 60751302 is a 600 V substation control cable with 4 stranded 12 AWG bare copper conductors, flame retardant cross-linked polyethylene (FR-XLPE) insulation and a black thermoset chlorinated polyethylene (CPE) jacket. The construction includes a rip cord for jacket removal. Conductors are color coded to ICEA S-58-679 Method 1 Table 2. Conductor temperature is not to exceed 90°C in continuous operation in wet and dry locations, 130°C under emergency overload and 250°C under short-circuit conditions.
Southwire 60751302 Technical Specs
Conductors
| Number of Conductors | 4 |
|---|---|
| Conductor Size | 12 AWG |
| Strands per Conductor | 7 |
| Conductor | Bare copper, class B compressed stranding |
| Color Code | ICEA S-58-679 Method 1 Table 2 |
| Conductor Colors | BLACK/RED/BLUE/ORANGE |
Insulation and Jacket
| Insulation | Flame retardant cross-linked polyethylene (FR-XLPE) |
|---|---|
| Insulation Thickness | 30 mils (0.76 mm) |
| Core | Polypropylene filler |
| Rip Cord | Yes |
| Jacket | Thermoset chlorinated polyethylene (CPE) |
| Jacket Color | Black |
Electrical
| Voltage Rating | 600 V |
|---|
Dimensions and Weight
| Nominal Outside Diameter | 476 mils (12.10 mm) |
|---|---|
| Nominal Total Weight | 154 lbs/1000 ft (230 kg/km) |
Standards
| ASTM B3 | Soft or annealed copper wire |
|---|---|
| ASTM B8 | Concentric-lay-stranded copper conductors |
| UL 1277 | Electrical power and control tray cables |
| UL 1685 FT4 | Vertical-tray fire propagation and smoke release test |
| ICEA S-58-679 | Control cable conductor identification |
| ICEA S-73-532 | Control, thermocouple extension and instrumentation cables |
| ICEA S-95-658 (NEMA WC70) | Power cables rated 2000 V or less for the distribution of electrical energy |
| IEEE 1202 FT4 | Vertical tray flame test (70,000 Btu/hr) |
| ICEA T-29-520 | Vertical tray flame test (210,000 Btu/hr) |
| VW-1 | Vertical-wire flame test |
Southwire 60751302 Applications
- Wet and dry areas.
- Installation in conduits, ducts, troughs and trays.
- Direct burial.
- Aerial runs supported by a messenger.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.