Southwire 60873799, Control Tray Cable 12 AWG 6C Copper THHN TC-ER 600V Black
Description
Southwire 60873799 is a 12 AWG 6-conductor control tray cable with bare copper conductors, PVC-with-nylon Type THHN or THWN insulation (VW-1 rated) and a black PVC jacket. It is Type TC-ER and rated 600V.
Southwire 60873799 Technical Specs
Construction
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 6 |
| Conductor | Class B compressed bare copper, 7 strands, per ASTM B3 and B8 |
| Strands per Conductor | 7 |
| Insulation | Polyvinyl chloride (PVC) with nylon layer, Type THHN or THWN (VW-1 rated) |
| Conductor Identification | Black, Red, Blue, Orange, Yellow, Brown (ICEA S-58-679 Method 1, Table 2) |
| Filler / Binder | Polyester flat thread binder tape |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Colour | Black |
| Type Designation | TC-ER |
Dimensions and Weight
| Insulation Thickness | 20 mils (0.51 mm) |
|---|---|
| Jacket Thickness | 45 mils (1.14 mm) |
| Approx. Overall Diameter | 0.481 in (1.22 cm) |
| Minimum Bend Radius | 1.9 in (4.83 cm) |
| Copper Weight | 122 lbs/1000 ft (182 kg/km) |
| Approx. Total Weight | 189 lbs/1000 ft (281 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 600V |
|---|---|
| Conductor Temperature | 75°C wet, 90°C dry; 105°C emergency overload; 250°C short circuit |
| DC Resistance at 25°C | 1.662 ohms/1000 ft |
| AC Resistance at 75°C | 2.002 ohms/1000 ft |
| Allowable Ampacity, Raceway, 75°C | 20 A |
| Allowable Ampacity, Raceway, 90°C | 24 A |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 1 Table 2 |
| ICEA S-73-532 | Control, Thermocouple Extension and Instrumentation Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 60873799 Applications
- Wet and dry areas, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial runs supported by a messenger.
- Class I, II and III, Division 2 per NEC Article 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.