Southwire 61005902 is an Armorlite® jacketed Type MC cable with four 12 AWG solid copper THHN/THWN conductors (black, white, red and blue) and a green insulated ground under aluminum interlocked armor, finished with a black sunlight-resistant, corrosion-resistant PVC jacket. Conductors are rated 90°C dry / 75°C wet, and the cable is suitable for wet locations per NEC 330.10(A)(11).
Southwire 61005902 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 4, plus a grounding conductor |
| Conductor | Solid copper per ASTM B3 |
| Conductor Colors | Black, White, Red, Blue |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
Grounding, Armor and Jacket
| Ground | Green insulated polyvinyl chloride with nylon sheath, Type THHN/THWN |
|---|---|
| Ground Size | 1x12 |
| Binder | Mylar tape |
| Armor | Aluminum interlocked armor |
| Jacket | Black polyvinyl chloride (PVC), sunlight resistant, corrosion resistant |
| Jacket Thickness | 50 mils (1.27 mm) |
Dimensions and Weight
| Diameter Over Armor | 0.553 in (1.40 cm) |
|---|---|
| Approximate Overall Diameter | 0.659 in (1.67 cm) |
| Approximate Weight | 240 lbs per 1,000 ft (357 kg/km) |
Ratings
| Conductor Temperature Rating | 90°C dry / 75°C wet (Type THHN/THWN) |
|---|---|
| Location | Wet locations per NEC 330.10(A)(11) |
| Anti-Short Bushing | Not required |
Standards and Compliance
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Federal Specification | Meets or exceeds A-A59544 (formerly J-C-30B) |
| NFPA 70 (NEC) | Meets or exceeds Article 330 |
Southwire 61005902 Applications
- Branch and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Locations exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC Article 645.
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.