Southwire 61066925, Metal Clad Cable 12 AWG 3C Neutral Per Phase Solid Copper THHN
Description
Southwire 61066925 is an Armorlite® neutral-per-phase Type MC cable with three 12 AWG solid copper THHN/THWN phase conductors, three 12 AWG neutrals and two 12 AWG insulated grounds under aluminum interlocked armor. The conductors are rated 90°C dry, and as unjacketed Type MC the cable is for dry, indoor locations only.
Neutral-per-phase construction complies with NEC 200.4 requirements for the installation and marking of neutral conductors. Neutrals are not to be used for more than one circuit (branch, multiwire branch, or ungrounded feeder).
Southwire 61066925 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Phase Conductors | 3 |
| Neutral Conductors | 3 x 12 AWG |
| Conductor | Solid copper per ASTM B3 |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.080 in (0.20 cm) |
Grounding and Armor
| Grounding | Two insulated grounds, polyvinyl chloride with nylon sheath Type THHN/THWN |
|---|---|
| Ground Size | 2x12 |
| Binder | Mylar tape, with a binder tape carrying the print legend wrapped around the assembly |
| Armor | Aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.616 in (1.56 cm) |
|---|---|
| Approximate Weight | 238 lbs per 1,000 ft (354 kg/km) |
Ratings
| Conductor Temperature | 90°C dry (Type THHN/THWN) |
|---|---|
| Location | Dry, indoor locations only per NEC 330.10(A)(10) |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 61066925 Applications
- Circuits affected by harmonics generated from non-linear switching loads, such as computers, variable frequency drives, electrical test equipment and office equipment.
- Multiple circuits for branch, feeder and service power distribution in commercial, industrial, institutional and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.