Southwire 61859125, Medium Voltage Cable 500 KCMIL 1C Aluminum 35 kV 420 mil TRXLP 16x12CN
Description
Southwire 61859125 is a HI-DRI Primary UD TRXLP Cable rated 35 kV: a single-conductor medium voltage cable built on a 500 KCMIL, 37-strand moisture blocked reverse lay compressed stranded 1350-H16/26 aluminum phase conductor. Its 420 mils of tree-retardant cross-linked polyethylene insulation, at a 133% insulation level, sit between a semi-conducting cross-linked polyethylene strand shield and insulation shield. A concentric neutral of bare copper wires (16x12CN) lies under a sunlight resistant, -40°C rated linear low density polyethylene jacket with red extruded stripes.
Southwire 61859125 Technical Specs
Conductor
| Conductor Size | 500 KCMIL |
|---|---|
| Number of Conductors | 1 |
| Strands | 37 |
| Conductor | Moisture blocked reverse lay compressed stranded 1350-H16/26 aluminum |
| Strand Shield | Semi-conducting cross-linked polyethylene |
Insulation and Shielding
| Insulation | Tree-retardant cross-linked polyethylene (TRXLP) |
|---|---|
| Insulation Thickness | 420 mils (10.67 mm) |
| Insulation Level | 133% |
| Insulation Shield | Semi-conducting cross-linked polyethylene |
Neutral and Jacket
| Concentric Neutral | Bare copper wires, 16x12CN |
|---|---|
| Jacket | Insulating linear low density polyethylene; sunlight resistant, -40°C rated |
| Jacket Identification | Surface print; lightning bolt symbol for supply cables indented in the jacket; red extruded stripes |
Dimensions and Weight
| Nominal Outside Diameter | 2,124 mils (53.96 mm) |
|---|---|
| Nominal Total Weight | 2,078 lbs/1000 ft (3,093 kg/km) |
Ratings
| Voltage | 35 kV; for use at 35,000 volts or less |
|---|---|
| Conductor Temperature | Not to exceed 90°C, normal operation |
Standards Met or Exceeded
| ASTM | ASTM B231, ASTM B609, ASTM B3 |
|---|---|
| Other Documents | ICEA S-94-649, AEIC CS-8, RUS U-1 |
Southwire 61859125 Applications
- Used predominantly for primary underground distribution in conduit systems.
- Wet or dry locations, direct burial and underground duct, including installations exposed to sunlight.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.