Southwire 62148815, Medium Voltage Cable 2 AWG 1C Aluminum 15 kV 133% EPR 10x14CN
Description
Southwire 62148815 is a 15 kV single-conductor medium voltage cable with a 2 AWG, 7-strand moisture blocked unilay compressed stranded 1350-H16/26 aluminum phase conductor, part of the Southwire 15kV Primary UD EPR Cable line. Its 220 mil ethylene propylene rubber (EPR) insulation is applied at a 133% insulation level between semi-conducting cross-linked polyethylene strand and insulation shields. A concentric neutral of bare copper wires (10x14CN) sits under a sunlight resistant, -40°C rated linear low density polyethylene jacket.
Southwire 62148815 Technical Specs
Conductor
| Conductor Size | 2 AWG |
|---|---|
| Number of Conductors | 1 |
| Strands | 7 |
| Conductor | Moisture blocked unilay compressed stranded 1350-H16/26 aluminum |
| Strand Shield | Semi-conducting cross-linked polyethylene |
Insulation and Shielding
| Insulation | Ethylene propylene rubber (EPR) |
|---|---|
| Insulation Thickness | 220 mils (5.59 mm) |
| Insulation Level | 133% |
| Insulation Shield | Semi-conducting cross-linked polyethylene |
Neutral and Jacket
| Concentric Neutral | Bare copper wires, 10x14CN |
|---|---|
| Jacket | Insulating linear low density polyethylene; sunlight resistant, -40°C rated |
| Jacket Marking | Surface print, with the lightning bolt symbol for supply cables indented |
Dimensions and Weight
| Nominal Outside Diameter | 1,071 mils (27.21 mm) |
|---|---|
| Nominal Total Weight | 581 lbs/1000 ft (865 kg/km) |
Ratings
| Voltage | 15 kV; for use at 15,000 volts or less |
|---|---|
| Conductor Temperature | Not to exceed 105°C, normal operation |
Standards
Meets or exceeds the following specifications.
| ASTM B609 | Aluminum 1350 round wire, annealed and intermediate tempers, for electrical purposes |
|---|---|
| ASTM B231 | Aluminum 1350 conductors, concentric-lay-stranded |
| ASTM B3 | Soft annealed copper wire |
| ICEA / AEIC / RUS | ICEA S-94-649, AEIC CS-8, RUS U-1 |
Southwire 62148815 Applications
- Primary underground distribution, predominantly in conduit systems.
- Wet or dry locations, direct burial and underground duct, including runs exposed to sunlight.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.