Southwire 62218601, Substation Cable 12 AWG 12C Copper FR-XLPE Thermoset CPE Jacket 600 V
Description
Southwire 62218601 is a 12 AWG, 12-conductor 600 V substation control cable with 7-strand class B compressed bare copper conductors, flame retardant cross-linked polyethylene (FR-XLPE) insulation and a thermoset chlorinated polyethylene (CPE) jacket. Conductor temperature ratings are 90°C for continuous operation in wet and dry locations, 130°C for emergency overload and 250°C for short circuit conditions.
Southwire 62218601 Technical Specs
Conductors and Rating
| Number of Conductors | 12 |
|---|---|
| Conductor Size | 12 AWG |
| Strands per Conductor | 7 |
| Conductor | Class B compressed bare copper |
| Voltage Rating | 600 V |
| Conductor Identification | ICEA S-58-679 Method 1 Table 2 |
| Conductor Colors | BLACK / RED / BLUE / ORANGE / YELLOW / BROWN / RED-BLACK STRIPE / BLUE-BLACK STRIPE / ORANGE-BLACK STRIPE / YELLOW-BLACK STRIPE / BROWN-BLACK STRIPE / BLACK-RED STRIPE |
Insulation and Jacket
| Insulation | FR-XLPE (flame retardant cross-linked polyethylene) |
|---|---|
| Insulation Thickness | 30 mils (0.76 mm) |
| Binder | Polyester flat thread binder tape |
| Jacket | Thermoset chlorinated polyethylene (CPE) |
Dimensions and Weight
| Nominal Outside Diameter | 759 mils (19.28 mm) |
|---|---|
| Nominal Total Weight | 414 lbs/1000 ft (616 kg/km) |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 | FT4 Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification |
| ICEA S-73-532 | Control, Thermocouple Extension and Instrumentation Cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 | FT4 Vertical Tray Flame Test (70,000 Btu/hr) |
| ICEA T-29-520 | 210,000 Btu/hr |
| VW-1 | Vertical-Wire Flame Test |
Southwire 62218601 Applications
- Wet and dry locations.
- Runs in conduit, ducts and troughs.
- Cable tray installations.
- Direct burial.
- Aerial installation supported by a messenger.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.