Southwire 62799899, Medium Voltage Cable 2/0 AWG 1C Copper 35 kV 100% EPR 13x10CN Red Stripe
Description
Southwire 62799899 is a 35kV Primary UD EPR Cable: a 35 kV single-conductor medium voltage cable built on a 2/0 AWG, 19-strand moisture blocked reverse lay, compressed stranded soft drawn copper conductor. It has 345 mils of ethylene propylene rubber (EPR) insulation at a 100% insulation level, between a semi-conducting cross-linked polyethylene strand shield and a semiconducting cross-linked polyethylene insulation shield. A concentric neutral of bare copper wires (13x10CN) is applied over the insulation shield, under a sunlight resistant, -40°C rated linear low density polyethylene jacket with red extruded stripes.
Southwire 62799899 Technical Specs
Conductor
| Conductor Size | 2/0 AWG |
|---|---|
| Number of Conductors | 1 |
| Strands | 19 |
| Conductor | Moisture blocked reverse lay, compressed stranded soft drawn copper |
| Strand Shield | Semi-conducting cross-linked polyethylene |
Insulation and Shielding
| Insulation | Ethylene propylene rubber (EPR) |
|---|---|
| Insulation Thickness | 345 mils (8.76 mm) |
| Insulation Level | 100% |
| Insulation Shield | Semiconducting cross-linked polyethylene |
Neutral and Jacket
| Concentric Neutral | Bare copper wires, 13x10CN |
|---|---|
| Jacket | Insulating linear low density polyethylene; sunlight resistant, -40°C rated |
| Jacket Marking | Surface print, with the lightning bolt symbol for supply cables indented; red extruded stripes |
Dimensions and Weight
| Nominal Outside Diameter | 1,539 mils (39.11 mm) |
|---|---|
| Nominal Total Weight | 1,635 lbs/1000 ft (2,433 kg/km) |
Ratings
| Voltage | 35 kV; for use at 35,000 volts or less |
|---|---|
| Conductor Temperature | Not to exceed 105°C, normal operation |
Standards
Meets or exceeds the following specifications:
| ASTM B3 | Soft Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft |
| Other Documents | ICEA S-94-649, AEIC CS-8, RUS U-1 |
Southwire 62799899 Applications
- Primary underground distribution in conduit systems.
- Wet or dry locations, direct burial and underground duct, including installations exposed to sunlight.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.