Southwire 64091799, Armored Cable 350 KCMIL 3C Copper 5 kV 133% / 8 kV 100% Orange
Description
Southwire 64091799 is a 350 KCMIL three-conductor HVTECK medium-voltage armored power cable rated 5 kV 133% / 8 kV 100%. Each of its three 37-strand copper conductors carries 115 mils of TR-XLPE with semi-conducting conductor and insulation shields and a 5 mil copper tape shield, and one 3 AWG bare copper grounding conductor runs with them. A PVC inner jacket, aluminum interlocked armor (AIA) and an orange PVC outer jacket complete the cable.
Southwire 64091799 Technical Specs
Conductors & Insulation
| Conductor Size | 350 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strands per Conductor | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | Tree-retardant cross-linked polyethylene (TR-XLPE) |
| Insulation Thickness | 115 mils (2.92 mm) |
| Diameter Over Conductor | 0.661 in (1.68 cm) |
| Diameter Over Insulation | 0.917 in (2.33 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 0.977 in (2.48 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One 3 AWG bare copper grounding conductor, Class B compressed stranded |
|---|---|
| Filler | Non-hydroscoping, non-wicking interstice fillers |
| Binder | Polypropylene tape |
| Inner Jacket | PVC |
| Inner Jacket Thickness | 110 mils (2.79 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 2.724 in (6.92 cm) |
| Outer Jacket | Orange polyvinyl chloride (PVC) |
| Jacket Thickness | 75 mils (1.91 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 2.874 in (7.30 cm) |
|---|---|
| Approximate Weight | 5967 lbs/1000 ft (8880 kg/km) |
| Maximum Pull Tension | 8400 lbs (3810.17 kg) |
| Minimum Bend Radius | 20.1 in (51.05 cm) |
Ratings & Compliance
| Voltage Rating | 5 kV 133% / 8 kV 100% |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -40°C (CSA LTGG, per C68.10, cold bend and impact) |
| Location Rating | HL rating per CSA HL |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B3 Soft or Annealed Copper Wire; ASTM B8 Concentric-Lay-Stranded Copper Conductors; CSA C22.2 No. 174; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA T-29-520 Flame Test (210,000 BTU/Hr); IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test; FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test); AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 64091799 Applications
- HVTECK is a CSA armored cable for industrial and commercial medium-voltage applications.
- Cable trays, duct banks, direct burial, troughs and continuous rigid cable supports; it is also concrete encaseable.
- Its construction is sunlight and moisture resistant, corona resistant, resistant to most chemical soils and acids, and flame retardant.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.