Southwire 64112703, Building Wire 350 kcmil Aluminum THHN-THWN-2 Tan
Description
Southwire 64112703 is a 350 kcmil aluminum SIMpull THHN/THWN-2 building wire in tan, from Southwire's line with AlumaFlex Brand conductors. Its 35-strand aluminum conductor is insulated with heat and moisture resistant PVC under a nylon jacket utilizing SIMpull Technology, and installs without a pulling lubricant. The voltage is 600 volts for all applications.
Southwire 64112703 Technical Specs
Construction
| Conductor Size | 350 kcmil |
|---|---|
| Number of Conductors | 1 |
| Conductor | Class B compact stranded bare aluminum per ASTM B800 and ASTM B801, or Single Input Wire (SIW) compact aluminum per ASTM B836 |
| Strand Count | 35 |
| Insulation | Heat and moisture resistant PVC |
| Sheath | Nylon, utilizing SIMpull Technology |
| Type Designation | THHN-THWN-2 |
| Insulation Colour | Tan |
Dimensions and Weight
| Diameter Over Conductor | 0.615 in (1.56 cm) |
|---|---|
| Insulation Thickness | 60 mils (1.52 mm) |
| Nylon Sheath Thickness | 5 mils (0.13 mm) |
| Approx. Overall Diameter | 0.758 in (1.93 cm) |
| Aluminum Content Weight | 329 lbs/1000 ft (490 kg/km) |
| Approx. Total Weight | 423 lbs/1000 ft (629 kg/km) |
Ratings
| Voltage | 600 volts, all applications |
|---|---|
| THHN | Dry locations, not to exceed 90°C |
| THWN-2 | Wet or dry locations not to exceed 90°C, or 75°C when exposed to oil |
Features
| Sunlight | Sunlight Resistant, sizes #2 and larger |
|---|---|
| Oil and Gasoline | Oil and Gasoline Resistant II |
| Cable Tray | CT, sizes 1/0 AWG and larger |
| Flame Tests | VW-1 and FT1, all sizes |
| RoHS | Compliant |
Standards
| ASTM B800 | 8000 Series Aluminum Alloy Wire |
|---|---|
| ASTM B801 | Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy |
| ASTM B836 | Compact Rounded Stranded Aluminum Conductors |
| UL 83 | Thermoplastic Insulated Wires and Cables |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| Federal Specification | A-A-59544 |
Southwire 64112703 Applications
- Pulled into conduit and cable trays for services, feeders and branch circuits in commercial or industrial applications, as specified in the National Electrical Code and other applicable codes and standards.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.