Southwire 64124201, Metal Clad Cable 12 AWG 2C with Ground Solid Copper THHN Green Armor
Description
Southwire 64124201 is an MC-AP™ HCF Type MC all purpose health care facility cable with two 12 AWG solid copper THHN/THWN conductors, black and white-black, a green insulated ground and a bare 8000 series aluminum grounding/bonding conductor under green aluminum interlocked armor. The armor is in contact with the aluminum grounding/bonding conductor as a redundant equipment grounding path. Conductors are rated 90°C dry.
Southwire 64124201 Technical Specs
Conductors and Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 2, plus two grounding conductors |
| Conductor | Solid copper per ASTM B3 |
| Conductor Colors | Black, White-Black |
| Insulation | Polyvinyl chloride with nylon sheath, Type THHN/THWN |
| Insulation Thickness | 20 mils (0.51 mm) |
| Diameter Over Conductor | 0.08 in (0.20 cm) |
Grounding and Armor
| Grounding | Green insulated ground, polyvinyl chloride with nylon sheath Type THHN/THWN, with redundant grounding by a bare 8000 series aluminum grounding/bonding conductor and the armor |
|---|---|
| Armor Grounding | Armor in contact with the aluminum grounding/bonding conductor serves as a redundant equipment grounding path component |
| Binder | Mylar tape, with a binder tape carrying the print legend wrapped around the assembly |
| Armor | Green aluminum interlocked armor |
Dimensions and Weight
| Diameter Over Armor | 0.506 in (1.29 cm) |
|---|---|
| Approximate Weight | 117 lbs per 1,000 ft (174 kg/km) |
Ratings
| Conductor Temperature | 90°C dry (Type THHN/THWN) |
|---|
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| UL 83 | Thermoplastic Insulated Wires and Cables |
| UL 1569 | Metal-Clad Cables |
| UL 1479 | Standard for Safety Fire Tests of Penetration Firestops |
| UL 1685 FT4 | Vertical-Tray Fire Propagation and Smoke Release Test |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| RoHS-2 | European Directive 2011/65/EU |
| Buy American | Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j), when ordered as “Made in the USA Only!” |
| Meets or Exceeds | Federal Specification A-A59544 (formerly J-C-30B); NFPA 70 (National Electrical Code), Article 330 |
Southwire 64124201 Applications
- Branch-circuit wiring for patient care areas of hospitals, medical centers and other health care facilities, including nursing homes, dental offices, clinics and outpatient facilities, when installed per NEC Articles 517 and 330 and mechanically protected per Article 300.4. Use in classified anesthetizing areas is prohibited.
- Circuits requiring redundant, dedicated or isolated grounding paths.
- Fished or embedded in plaster.
- Concealed or exposed runs.
- Environmental air-handling spaces per NEC 300.22(C).
- Places of assembly per NEC 518.4 and theaters per NEC 520.5.
- Cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) and 645.5(D)(2).
- Class I Div. 2, Class II Div. 2 and Class III Div. 1.
- Use with UL Listed MCI-A fittings.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.