Southwire 64336999, Machine Flex Flexible Tray Cable 6 AWG 4C Copper TC-ER 600V Gray
Description
Southwire 64336999 is a 6 AWG, 4-conductor Machine Flex flexible tray cable with Class K flexible stranded bare annealed copper conductors, polyvinyl chloride (PVC) with nylon layer Type THHN insulation and a gray sunlight resistant thermoplastic elastomer (TPE) jacket. It is Type TC-ER/WTTC/MTW/DP-1 and rated 600V. One of the 4 conductors is a green ground with a yellow stripe.
Southwire 64336999 Technical Specs
Construction
| Conductor Size | 6 AWG |
|---|---|
| Number of Conductors | 4, including one green ground with yellow stripe |
| Conductor Material | Class K flexible stranded bare annealed copper per ASTM B3, B172 and B174 |
| Strands per Conductor | 259 |
| Insulation | Polyvinyl chloride (PVC) with nylon layer, Type THHN |
| Grounding Conductor | One green ground with yellow stripe, Type THHN |
| Jacket | Sunlight resistant thermoplastic elastomer (TPE) |
| Jacket Colour | Gray |
| Type Designation | TC-ER/WTTC/MTW/DP-1 |
| Appliance Wiring Material | AWM 2587 |
| Cold Impact | -40°C |
Dimensions and Weight
| Diameter Over Conductor | 0.198 in (0.50 cm) |
|---|---|
| Insulation Thickness | 35 mils (0.89 mm) |
| Jacket Thickness | 70 mils (1.78 mm) |
| Approx. Overall Diameter | 0.817 in (2.08 cm) |
| Minimum Bend Radius | 3.2 in (8.13 cm) |
| Copper Content Weight | 358 lbs/1000 ft (533 kg/km) |
| Approx. Total Weight | 562 lbs/1000 ft (836 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 600V |
|---|---|
| Conductor Temperature | 75°C in wet locations and 90°C in dry locations; 130°C emergency overload; 150°C short circuit |
| DC Resistance at 25°C | 0.450 ohms/1000 ft |
| AC Resistance at 75°C | 0.541 ohms/1000 ft |
| Allowable Ampacity, Raceway, 75°C | 52 A |
| Allowable Ampacity, Raceway, 90°C | 60 A |
Standards
| ASTM B172 | Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors |
|---|---|
| ASTM B174 | Standard Specification for Bunch-Stranded Copper |
| UL 83 | Thermoplastic Insulated Wire and Cables (sizes 14 AWG to 1000 kcmil) |
| UL 758 | AWM Style 2587 |
| UL 1063 | Machine Tool Wiring (MTW) |
| UL 1277 | TC-ER |
| UL 1690 | Data Processing Cable (DP-1) |
| UL 2277 | Type WTTC |
| CSA C22.2 No.230 | Tray Cables - Rated TC |
| CSA C22.2 No. 239 | Control and instrumentation cables |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| Ecolab PM-40-1 | Exceeds the Material Resistance Test With 30-day Exposure, UL Verified V747862 |
| NFPA 79 | Electrical Standard for Industrial Machinery |
CE/RoHS-2: the CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive.
Made in America: compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661.
Southwire 64336999 Applications
- Industrial machinery wiring conforming to NFPA 79.
- Wet and dry areas, conduits, ducts, troughs, cable trays and direct burial.
- Class I, II, Division 2 per NEC Article 501 and 502.
- Exposed runs (TC-ER) per NEC 336.10.
- CNC machines, grinding, cutting, metal forming, buffing, bottling equipment and conveyors.
- Processing and packaging equipment, assembly lines, control panels and food and beverage plants.
- Oil sands, plant expansion, wind energy and data centers.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.