Southwire 64641424, Bare Aluminum Conductor ACSS 795 KCMIL 26/7 DRAKE
Description
Southwire 64641424 is a bare 795 KCMIL ACSS (Aluminum Conductor, Steel Supported) overhead conductor with the codeword DRAKE. Two or more layers of aluminum 1350-O wire, 26 strands in the fully annealed (soft) temper, are stranded around a 7-wire steel core that carries most or all of the mechanical load. The steel core wires are protected from corrosion by a zinc-5% aluminum-mischmetal alloy coating. Nominal outside diameter is 1107 mils and nominal total weight 1093 lbs per 1000 ft.
Southwire 64641424 Technical Specs
Conductor
| Codeword | DRAKE |
|---|---|
| Conductor Type | ACSS (Aluminum Conductor, Steel Supported) |
| Southwire Designation | 795-26/7 ACSS/MA2/63% DRAKE |
| Conductor Size | 795 KCMIL |
| Stranding (Aluminum/Steel) | 26/7 |
| Aluminum Wire | 1350-O, fully annealed (soft) temper |
| Core Designation | MA2 |
| Steel Core Coating | Zinc-5% aluminum-mischmetal alloy |
Dimensions and Weight
| Nominal Outside Diameter | 1107 mils (28.13 mm) |
|---|---|
| Nominal Total Weight | 1093 lbs/1000 ft (1627 kg/km) |
Standards
Its ACSS conductor meets or exceeds the following ASTM specifications.
| ASTM B500 | Metallic Coated Stranded Steel Core for Use in Overhead Electrical Conductors |
|---|---|
| ASTM B609 | Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes |
| ASTM B802 | Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR) |
| ASTM B803 | High-Strength Zinc-5% Aluminum Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors |
| ASTM B856 | Concentric-Lay-Stranded Aluminum Conductors, Coated Steel Supported (ACSS) |
| ASTM B958 | Extra-High-Strength and Ultra-High-Strength Class A Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for Use in Overhead Electrical Conductors |
Southwire 64641424 Applications
- ACSS is used for overhead distribution and transmission lines.
- It operates continuously at elevated temperatures up to 250°C without loss of strength.
- In Southwire's account it sags less than a comparable ACSR under electrical loadings, is self-damping if prestretched during installation, and keeps final sags unaffected by long-term creep of the aluminum.
- Reconductoring where more current is needed at existing tensions and clearances, new lines where reduced conductor sag lets structures be economized, new lines requiring high emergency loadings, and lines where aeolian vibration is a problem.
- Corrosion protection should be chosen to suit the environment the conductor will be exposed to.
Documents
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.