Southwire 64728099, Power Drop Cable 373.7 kcmil 3C Copper THHN TC-ER/WTTC 600V Black
Description
Southwire 64728099 is a 373.7 kcmil 3-conductor power drop cable with flexible stranded bare copper conductors, polyvinyl chloride (PVC) with nylon layer Type THHN insulation and a black polyvinyl chloride (PVC) jacket. It is Type TC-ER/WTTC and AWM 20886, rated 600V, with one 2 AWG green grounding conductor in addition to the three circuit conductors, and conforms to NFPA 79.
Southwire 64728099 Technical Specs
Construction
| Conductor Size | 373.7 kcmil |
|---|---|
| Number of Conductors | 3, plus one grounding conductor |
| Conductor Material | Flexible stranded bare copper per ASTM B3, B172 and B174 |
| Strands per Conductor | 931 |
| Insulation | Polyvinyl chloride (PVC) with nylon layer, Type THHN |
| Conductor Colours | Black, Red, Blue |
| Grounding Conductor | One 2 AWG, green; flexible stranded bare copper per ASTM B3, B172 and B174 |
| Filler | Polypropylene fillers as necessary for a round assembly |
| Binder | Mylar tape |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Colour | Black |
| Type Designation | TC-ER/WTTC |
| Appliance Wiring Material | AWM 20886 |
Dimensions and Weight
| Diameter Over Conductor | 0.710 in (1.80 cm) |
|---|---|
| Insulation Thickness | 70 mils (1.78 mm) |
| Jacket Thickness | 110 mils (2.79 mm) |
| Approx. Overall Diameter | 2.055 in (5.22 cm) |
| Copper Weight | 3539 lbs/1000 ft (5267 kg/km) |
| Approx. Total Weight | 4478 lbs/1000 ft (6664 kg/km) |
Electrical Ratings
| Voltage Rating | 600V |
|---|---|
| Conductor Temperature | 75°C in wet locations; 90°C in dry locations; 130°C emergency overload; 250°C short circuit |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B172 | Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors |
| ASTM B174 | Standard Specification for Bunch-Stranded Copper |
| UL 509 | Bus Drop Cable |
| UL 758 | Standard for Appliance Wiring Material Style 20886 |
| UL 1277 | TC-ER |
| UL 2277 | Type WTTC |
| CSA C22.2 No. 75 | Thermoplastic Insulated Wires and Cables |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
| CE/RoHS-2 | The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive |
Southwire 64728099 Applications
- Power feed drops.
- Wet and dry areas, in conduits, ducts, troughs and trays, including exposed runs (TC-ER) per NEC 336.10.
- Direct burial.
- Class I, II, Division 2 per NEC Article 501 and 502.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.