Southwire 65301999, Armored Cable 2/0 AWG 3C Copper 35 kV Black
Southwire · MPN 65301999
Description
Southwire 65301999 is a 2/0 AWG three-conductor HVTECK armored cable rated 35 kV at a 133% insulation level, built on 19-strand bare copper conductors. Every conductor is covered by a semi-conducting shield, 420 mils of tree-retardant cross-linked polyethylene (TRXLPE), a strippable insulation shield and a 5 mil copper tape shield, and a #6 AWG bare copper grounding conductor is cabled with them. Over a PVC inner jacket come aluminum interlocked armor (AIA) and a black PVC outer jacket.
Southwire 65301999 Technical Specs
Conductors & Insulation
| Conductor Size | 2/0 AWG |
|---|---|
| Number of Conductors | 3 |
| Strand Count | 19 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | Tree-retardant cross-linked polyethylene (TRXLPE) |
| Insulation Thickness | 420 mils (10.67 mm) |
| Conductor Colors | Black |
| Diameter Over Conductor | 0.405 in (1.03 cm) |
| Diameter Over Insulation | 1.284 in (3.26 cm) |
Shielding & Grounding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | 5 mil copper tape, helically wrapped with 25% overlap |
| Diameter Over Shield | 1.344 in (3.41 cm) |
| Grounding Conductor | One #6 AWG, Class B compressed stranded bare copper |
Jacket & Armor
| Filler | Non-hygroscopic, non-wicking fillers in the interstices |
|---|---|
| Binder | Polypropylene tape |
| Inner Jacket | PVC |
| Inner Jacket Thickness | 125 mils (3.18 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 3.566 in (9.06 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Nominal Outside Diameter | 3.736 in (9.49 cm) |
|---|---|
| Approximate Weight | 5,789 lbs/1000 ft (8615 kg/km) |
| Maximum Pull Tension | 3,194 lbs (1448.77 kg) |
| Minimum Bend Radius | 26.2 in (66.55 cm) |
Ratings
| Voltage Rating | 35 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- CSA C22.2 No. 174
- CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
- CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
- CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
- CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
- CSA HL rating
- CSA SUN RES - for Sunlight Resistant rating
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA T-29-520 Flame Test (210,000 BTU/Hr)
- IEEE 383 Flame Test (70,000 btu)
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
This 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL, with sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids, and flame retardance.