Southwire 65354899, Medium Voltage Cable 350 KCMIL 3C Copper 15 kV Black PVC
Description
Southwire 65354899 is a 15 kV shielded medium voltage power cable with three 350 KCMIL copper phase conductors of 37 strands and one 2 AWG bare copper grounding conductor, under a black PVC jacket. Each conductor carries 220 mils of TRXLPE insulation at the 133% insulation level between semi-conducting conductor and insulation shields, wrapped with a copper tape shield. Conductor temperature rating is 105°C for normal operation.
Southwire 65354899 Technical Specs
Construction
| Number of Conductors | 3, plus ground |
|---|---|
| Conductor Size (each conductor) | 350 KCMIL |
| Strands (each conductor) | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | Tree Retardant Cross Linked Polyethylene (TRXLPE), 133% insulation level |
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape with 25% overlap |
| Grounding Conductor | 1 x 2 AWG, Class B compressed stranded bare copper |
| Filler | Wax paper filler |
| Binder | Poly glass tape |
| Jacket | Polyvinyl Chloride (PVC) |
| Jacket Color | Black |
Dimensions and Weight
| Diameter Over Conductor (each conductor) | 0.661 in (1.68 cm) |
|---|---|
| Diameter Over Insulation (each conductor) | 1.147 in (2.91 cm) |
| Insulation Thickness (each conductor) | 220 mils (5.59 mm) |
| Diameter Over Shield (each conductor) | 1.207 in (3.07 cm) |
| Overall Jacket Thickness | 135 mils (3.43 mm) |
| Cable Overall Diameter (approx.) | 2.935 in (7.45 cm) |
| Cable Weight (approx.) | 5898 lbs/1000 ft (8777 kg/km) |
Installation Limits
| Maximum Pulling Tension | 8400 lbs (3810.17 kg) |
|---|---|
| Minimum Bending Radius | 20.5 in (52.07 cm) |
| Maximum Sidewall Pressure | 1000 lb/ft |
Ratings
| Voltage Class | 15 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -35°C |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 1072 | Medium-Voltage Power Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-93-639 (NEMA WC 74) | 5-46 KV Shielded Power Cable |
| AEIC CS-8 | Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Made in America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 65354899 Applications
- Wet and dry locations.
- Installation in conduits, ducts and troughs.
- Direct burial.
- Class I and II, Division 2 per NEC Article 501 and 502.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.