Southwire 66822799, Armored Cable 12 AWG 2C Copper 1 kV Black
Description
Southwire 66822799 is a 12 AWG two-conductor Type TECK 90 armored control cable rated 1 kV, with 7-strand copper conductors insulated in cross-linked polyethylene (XLPE) and colored black and white. An uninsulated #14 AWG grounding conductor is included, and a black PVC inner jacket lies beneath aluminum interlocked armor (AIA) and a black low smoke zero halogen (LSZH) outer jacket.
Southwire 66822799 Technical Specs
Conductors & Insulation
| Conductor Size | 12 AWG |
|---|---|
| Number of Conductors | 2 |
| Strand Count | 7 |
| Conductor | Class B stranded copper, compressed or compact, per ASTM B3 and B8 |
| Insulation | Cross-linked polyethylene (XLPE) |
| Insulation Thickness | 45 mils (1.14 mm) |
| Conductor Colors | Black, White |
| Diameter Over Conductor | 0.088 in (0.22 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One #14 AWG, uninsulated Class B stranded |
|---|---|
| Inner Jacket | Black polyvinyl chloride (PVC) |
| Inner Jacket Thickness | 50 mils (1.27 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 0.675 in (1.71 cm) |
| Outer Jacket | Black low smoke zero halogen (LSZH) |
| Jacket Thickness | 45 mils (1.14 mm) |
Dimensions & Weight
| Nominal Outside Diameter | 0.765 in (1.94 cm) |
|---|---|
| Approximate Weight | 259 lbs/1000 ft (385 kg/km) |
| Maximum Pull Tension | 104 lbs (47.17 kg) |
| Minimum Bend Radius | 5.3 in (13.46 cm) |
Ratings
| Voltage Rating | 1 kV |
|---|---|
| Type | TECK 90 |
| Max. Continuous Operating Temperature | 90°C |
| CSA Cold Bend and Impact Temperature | -40°C |
| Min. Installation Temperature | -40°C |
| Maximum Sidewall Pressure | 1000 lbs/ft |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- CSA C22.2 No. 174
- CSA C22.2 No. 131 Type TECK 90 Cable
- CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
- CSA ST1 Smoke Test - marked FT4-ST1
- CSA SUN RES - for Sunlight Resistant rating
- CSA AG14 - Acid Gas Compliance
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems
Southwire 66822799 Applications
- Exposed or concealed wiring in wet or dry locations.
- Ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway, in wet, dry or classified locations.
- Sunlight resistant.
- Control, lighting and power circuits in pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
- Projects that call for the flame spread and smoke release requirements of NFPA 130, which this line meets.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.