Southwire 66826199, Armored Cable 350 KCMIL 3C Copper 35 kV Orange
Description
Southwire 66826199 is a 350 KCMIL three-conductor medium-voltage armored cable rated 35 kV at a 133% insulation level. Its 37-strand compressed bare copper conductors carry a semi-conducting conductor shield, 420 mils of no-lead ethylene propylene rubber (NL-EPR), a strippable insulation shield and a 5 mil copper tape shield, with one #2 AWG bare copper grounding conductor. Finishing the cable are ARMOR-X® continuous corrugated welded armor and an orange PVC outer jacket.
Southwire 66826199 Technical Specs
Conductors & Insulation
| Conductor Size | 350 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strand Count | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 420 mils (10.67 mm) |
| Conductor Colors | Black |
| Diameter Over Conductor | 0.661 in (1.68 cm) |
| Diameter Over Insulation | 1.527 in (3.88 cm) |
Shielding & Grounding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | 5 mil copper tape, helically wrapped with 25% overlap |
| Diameter Over Shield | 1.587 in (4.03 cm) |
| Grounding Conductor | One #2 AWG, Class B compressed stranded bare copper |
Jacket & Armor
| Filler | Wax paper |
|---|---|
| Binder | Polypropylene tape |
| Armor | ARMOR-X® continuous corrugated welded armor |
| Diameter Over Armor | 3.850 in (9.78 cm) |
| Outer Jacket | Orange polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Nominal Outside Diameter | 4.028 in (10.23 cm) |
|---|---|
| Approximate Weight | 8,576 lbs/1000 ft (12762 kg/km) |
| Maximum Pull Tension | 8,400 lbs (3810.17 kg) |
| Minimum Bend Radius | 28.1 in (71.37 cm) |
Ratings
| Voltage Rating | 35 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -50°C |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 1072 Medium-Voltage Power Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
It is made in America and compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661.
Southwire 66826199 Applications
- Wet and dry areas, including runs in conduits, ducts, troughs and trays.
- Direct burial installations.