Southwire 66836599, Armored Cable 4/0 AWG 1C Copper 25 kV Black
Southwire · MPN 66836599
Description
Southwire 66836599 is a 4/0 AWG single-conductor HVTECK armored cable rated 25 kV at a 133% insulation level. Its 19-strand bare copper conductor carries a semi-conducting conductor shield, 320 mils of no-lead ethylene propylene rubber (NL-EPR), a strippable insulation shield and a helically wrapped 5 mil copper tape shield. A PVC inner jacket sits under aluminum interlocked armor (AIA), finished with a black PVC outer jacket.
Southwire 66836599 Technical Specs
Conductors & Insulation
| Conductor Size | 4/0 AWG |
|---|---|
| Number of Conductors | 1 |
| Strand Count | 19 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 320 mils (8.13 mm) |
| Diameter Over Conductor | 0.512 in (1.30 cm) |
| Diameter Over Insulation | 1.176 in (2.99 cm) |
Shielding & Grounding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | 5 mil copper tape, helically wrapped with 25% overlap |
| Diameter Over Shield | 1.236 in (3.14 cm) |
Jacket & Armor
| Inner Jacket | PVC |
|---|---|
| Inner Jacket Thickness | 80 mils (2.03 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.760 in (4.47 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 60 mils (1.52 mm) |
Dimensions & Weight
| Nominal Outside Diameter | 1.880 in (4.78 cm) |
|---|---|
| Approximate Weight | 2,013 lbs/1000 ft (2996 kg/km) |
| Maximum Pull Tension | 1,692 lbs (767.48 kg) |
| Minimum Bend Radius | 22.6 in (57.40 cm) |
Ratings
| Voltage Rating | 25 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Maximum Sidewall Pressure | 1000 lbs/ft |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- CSA C22.2 No. 174
- CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
- CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
- CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
- CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
- CSA HL rating
- CSA SUN RES - for Sunlight Resistant rating
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA T-29-520 Flame Test (210,000 BTU/Hr)
- IEEE 383 Flame Test (70,000 btu)
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
- FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
This 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL, with sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids, and flame retardance.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.