Southwire 66849799, Medium Voltage Cable 250 KCMIL Copper 8 kV Black CPE
Description
Southwire 66849799 is an 8 kV shielded medium voltage power cable with a single 250 KCMIL Class B compressed stranded bare copper conductor of 37 strands, 140 mils of NL-EPR insulation at the 133% insulation level, a helically wrapped 5 mil copper tape shield and a black thermoplastic chlorinated polyethylene (CPE-TP) jacket. Conductor temperature ratings are 105°C for normal operation, 140°C for emergency overload and 250°C for short circuit conditions.
Southwire 66849799 Technical Specs
Construction
| Number of Conductors | 1 |
|---|---|
| Conductor Size | 250 KCMIL |
| Strands | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | No lead ethylene propylene rubber (NL-EPR) |
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Jacket | Thermoplastic chlorinated polyethylene (CPE-TP) |
| Jacket Color | Black |
Dimensions and Weight
| Diameter Over Conductor | 0.558 in (1.42 cm) |
|---|---|
| Diameter Over Insulation | 0.884 in (2.25 cm) |
| Insulation Thickness | 140 mils (3.56 mm) |
| Diameter Over Shield | 0.944 in (2.40 cm) |
| Jacket Thickness | 80 mils (2.03 mm) |
| Overall Diameter (approx.) | 1.124 in (2.85 cm) |
| Weight (approx.) | 1,243 lbs/1000 ft (1,850 kg/km) |
Installation Limits
| Maximum Pulling Tension | 2,000 lbs (907.18 kg) |
|---|---|
| Minimum Bending Radius | 13.4 in (34.04 cm) |
| Maximum Sidewall Pressure | 1000 lb/ft |
Ratings
| Voltage Rating | 8 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -35°C when UL listed |
| CT Rating | CT rated 1/0 and larger |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 1072 | Medium-Voltage Power Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger) |
| CSA C22.2 No.230 | Tray Cables - Rated TC |
| CSA C22.2 No. 2556 / UL 2556 | Cable Test Methods |
| CSA C68.10 | Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV |
| ICEA S-93-639 (NEMA WC 74) | 5-46 KV Shielded Power Cable |
| ICEA S-97-682 | Standard for Shielded Utility Cable Rated for 5 - 46kV |
| AEIC CS-8 | Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| Buy America | Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661 |
Southwire 66849799 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and trays.
- Direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5).
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.