Southwire 66854499, Armored Cable 500 KCMIL 3C Copper 25 kV Orange
Description
Southwire 66854499 is a 500 KCMIL three-conductor medium-voltage armored cable rated 25 kV at a 133% insulation level. Its 37-strand compressed bare copper conductors carry a semi-conducting conductor shield, 320 mils of no-lead ethylene propylene rubber (NL-EPR), a strippable insulation shield and a 5 mil copper tape shield, with one #2/0 AWG bare copper grounding conductor. Finishing the cable are aluminum interlocked armor and an orange PVC outer jacket.
Southwire 66854499 Technical Specs
Conductors & Insulation
| Conductor Size | 500 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strand Count | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Insulation | No-lead ethylene propylene rubber (NL-EPR) |
| Insulation Thickness | 320 mils (8.13 mm) |
| Conductor Colors | Black |
| Diameter Over Conductor | 0.789 in (2.00 cm) |
| Diameter Over Insulation | 1.452 in (3.69 cm) |
Shielding & Grounding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | 5 mil copper tape, helically wrapped with 25% overlap |
| Diameter Over Shield | 1.512 in (3.84 cm) |
| Grounding Conductor | One #2/0 AWG, Class B compressed stranded bare copper |
Jacket & Armor
| Filler | Wax paper |
|---|---|
| Binder | Polypropylene tape |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 3.637 in (9.24 cm) |
| Outer Jacket | Orange polyvinyl chloride (PVC) |
| Jacket Thickness | 85 mils (2.16 mm) |
Dimensions & Weight
| Nominal Outside Diameter | 3.807 in (9.67 cm) |
|---|---|
| Approximate Weight | 9,330 lbs/1000 ft (13885 kg/km) |
| Maximum Pull Tension | 12,000 lbs (5443.10 kg) |
| Minimum Bend Radius | 26.6 in (67.56 cm) |
Ratings
| Voltage Rating | 25 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
Standards
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B496 Compact Round Concentric-lay-standard copper
- UL 1072 Medium-Voltage Power Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
It is made in America and compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661.
Southwire 66854499 Applications
- Wet and dry areas, including runs in conduits, ducts, troughs and trays.
- Direct burial installations.
- Class I, II, and III, Division 2 per NEC Article 501, 502, and 503.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.