Southwire 66924899, Armored Cable 350 KCMIL 3C Aluminum 5 kV Orange
Description
Southwire 66924899 is a 350 KCMIL three-conductor Type TECK 90 armored power cable rated 5 kV, of non-shielded construction. Its 35-strand compact 8000 Series aluminum conductors carry an extruded semi-conducting conductor shield and 90 mils of tree-retardant cross-linked polyethylene (TRXLPE), and one bare #2 aluminum grounding conductor is included. A black PVC inner jacket, aluminum interlocked armor (AIA) and an orange PVC outer jacket complete the cable.
Southwire 66924899 Technical Specs
Conductors & Insulation
| Conductor Size | 350 KCMIL |
|---|---|
| Number of Conductors | 3 |
| Strand Count | 35 |
| Conductor | Class B compact stranded 8000 Series aluminum ACM, per ASTM B801 |
| Conductor Shield | Extruded semi-conducting thermosetting polymeric layer |
| Insulation | Tree-retardant cross-linked polyethylene (TRXLPE), 90°C |
| Insulation Thickness | 90 mils (2.29 mm) |
| Diameter Over Conductor | 0.615 in (1.56 cm) |
Grounding, Armor & Jacket
| Grounding Conductor | One #2 AWG, Class B compact stranded 8000 Series bare aluminum |
|---|---|
| Binder | Polypropylene tape |
| Inner Jacket | Black PVC |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 2.402 in (6.10 cm) |
| Outer Jacket | Orange PVC |
Dimensions & Weight
| Nominal Outside Diameter | 2.534 in (6.44 cm) |
|---|---|
| Approximate Weight | 2,691 lbs/1000 ft (4005 kg/km) |
| Maximum Pull Tension | 6,300 lbs (2857.63 kg) |
| Minimum Bend Radius | 17.7 in (44.96 cm) |
Ratings
| Voltage Rating | 5 kV |
|---|---|
| Shielding | Non-shielded |
| Type | TECK 90 |
| Max. Continuous Operating Temperature | 90°C |
| Emergency Overload Temperature | 140°C |
| Short Circuit Temperature | 250°C |
| CSA Cold Bend and Impact Temperature | -40°C |
| Min. Installation Temperature | -25°C |
Standards
- CSA C22.2 No. 174
- CSA C22.2 No. 131 Type TECK 90 Cable
- CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
- CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
- CSA HL rating
- CSA SUN RES - for Sunlight Resistant rating
- CSA AG14 - Acid Gas Compliance
- ICEA S-96-659 (NEMA WC 71) 2001-5000 V Nonshielded Cables
- IEEE 383 Flame Test (70,000 btu)
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
The 5KV TECK 90 non-shielded TRXLPE power cable is a CSA approved armoured cable for industrial and commercial medium voltage applications, FT4, -40°C, HL, AG14 and 90°C rated for use in harsh Canadian environments.
Southwire 66924899 Applications
- Cable trays, duct banks and troughs.
- Direct burial, and installation encased in concrete.
- Classified locations.
- Continuous rigid cable supports.