Southwire 67192499, Medium Voltage Cable 500 KCMIL Copper 35 kV Black LSZH
Description
Southwire 67192499 is a 35 kV shielded medium voltage power cable with a single 500 KCMIL Class B compressed stranded bare copper conductor of 37 strands, 420 mils of NL-EPR insulation at the 133% insulation level, a helically wrapped 5 mil copper tape shield and a black thermoplastic low smoke zero halogen (LSZH-TP) jacket. Conductor temperature ratings are 105°C for normal operation, 140°C for emergency overload and 250°C for short circuit conditions.
Southwire 67192499 Technical Specs
Construction
| Number of Conductors | 1 |
|---|---|
| Conductor Size | 500 KCMIL |
| Strands | 37 |
| Conductor | Class B compressed stranded bare copper per ASTM B3 and B8 |
| Conductor Shield | Semi-conducting cross-linked copolymer |
| Insulation | No lead ethylene propylene rubber (NL-EPR) |
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Jacket | Thermoplastic low smoke zero halogen (LSZH-TP) |
| Jacket Color | Black |
Dimensions and Weight
| Diameter Over Conductor | 0.789 in (2.00 cm) |
|---|---|
| Diameter Over Insulation | 1.652 in (4.20 cm) |
| Insulation Thickness | 420 mils (10.67 mm) |
| Diameter Over Shield | 1.712 in (4.35 cm) |
| Jacket Thickness | 110 mils (2.79 mm) |
| Overall Diameter (approx.) | 1.952 in (4.96 cm) |
| Weight (approx.) | 3,016 lbs/1000 ft (4,488 kg/km) |
Installation Limits
| Maximum Pulling Tension | 4,000 lbs (1,814.37 kg) |
|---|---|
| Minimum Bending Radius | 23.4 in (59.44 cm) |
| Maximum Sidewall Pressure | 1000 lb/ft |
Ratings
| Voltage Rating | 35 kV |
|---|---|
| Insulation Level | 133% |
| Conductor Temperature | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Cold Bend | -35°C when UL listed |
| Low Smoke | ST1 rated for sizes 1/0 and larger |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 1072 | Medium-Voltage Power Cables |
| UL 1685 FT4-ST1 | Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger) |
| CSA C22.2 No.230 | Tray Cables - Rated TC-ER |
| CSA C22.2 No. 2556 / UL 2556 | Cable Test Methods |
| CSA C68.10 | Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV |
| ICEA S-93-639 (NEMA WC 74) | 5-46 KV Shielded Power Cable |
| IEEE 1202 | FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger) |
| AEIC CS-8 | Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
| NFPA 130 | Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger) |
Southwire 67192499 Applications
- Wet and dry locations.
- Installation in conduits, ducts, troughs and trays.
- Direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5).
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.