Southwire 67208599, Armored Cable 500 KCMIL 1C Aluminum 8 kV Black
Southwire · MPN 67208599
Description
Southwire 67208599 is a 500 KCMIL single-conductor HVTECK medium voltage armored cable rated 8 kV at 133% insulation level. Its 34-strand 8000 Series aluminum conductor carries 140 mils of TR-XLP insulation, with semi-conducting conductor and insulation shields and a 5 mil copper tape shield. A PVC inner jacket, aluminum interlocked armor (AIA) and a black polyvinyl chloride (PVC) outer jacket complete the cable. The 8kV HVTECK line is a CSA armoured cable for industrial and commercial medium voltage applications, rated FT4, -40°C and HL.
Southwire 67208599 Technical Specs
Conductors & Insulation
| Conductor Size | 500 KCMIL |
|---|---|
| Number of Conductors | 1 |
| Strands per Conductor | 34 |
| Conductor | Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836 |
| Conductor Separator | Used on this size (500 kcmil and larger) |
| Insulation | Tree-retardant cross-linked polyethylene (TR-XLP) |
| Insulation Thickness | 140 mils (3.56 mm) |
| Insulation Level | 133% |
| Diameter Over Conductor | 0.735 in (1.87 cm) |
| Diameter Over Insulation | 1.084 in (2.75 cm) |
Shielding
| Conductor Shield | Semi-conducting cross-linked copolymer |
|---|---|
| Insulation Shield | Strippable semi-conducting cross-linked copolymer |
| Metallic Shield | Helically wrapped 5 mil copper tape, 25% overlap |
| Diameter Over Shield | 1.144 in (2.91 cm) |
Grounding, Armor & Jacket
| Inner Jacket | PVC |
|---|---|
| Inner Jacket Thickness | 80 mils (2.03 mm) |
| Armor | Aluminum interlocked armor (AIA) |
| Diameter Over Armor | 1.656 in (4.21 cm) |
| Outer Jacket | Black polyvinyl chloride (PVC) |
| Jacket Thickness | 60 mils (1.52 mm) |
Dimensions & Weight
| Approximate Outside Diameter | 1.776 in (4.51 cm) |
|---|---|
| Approximate Weight | 1479 lbs/1000 ft (2201 kg/km) |
| Maximum Pull Tension | 3000 lbs (1360.78 kg) |
| Minimum Bend Radius | 21.3 in (54.10 cm) |
Ratings & Compliance
| Voltage Rating | 8 kV at 133% insulation level |
|---|---|
| Operating Temperatures | 105°C normal operation; 140°C emergency overload; 250°C short circuit |
| Location Rating | CSA HL |
| Maximum Sidewall Pressure | 1000 lbs/ft |
| Standards | ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy; ASTM B836 Compact Rounded Stranded Aluminum Conductors; CSA C22.2 No. 174; CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods; CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV; CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV; CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating; CSA HL rating; CSA SUN RES - for Sunlight Resistant rating; ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable; ICEA T-29-520 Flame Test (210,000 BTU/Hr); IEEE 383 Flame Test (70,000 btu); IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger); FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test); AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements) |
Southwire 67208599 Applications
- Industrial and commercial medium voltage installations.
- The line is sunlight and moisture resistant, flame retardant, exceptionally corona resistant and resistant to most chemical soils and acids.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.