Southwire 67223599, Power Tray Cable 500 kcmil 4C Copper XHHW-2 TC-ER 1000V Black
Description
Southwire 67223599 is a 500 kcmil, 4-conductor power tray cable with copper conductors, cross-linked polyethylene (XLPE) Type XHHW-2 insulation and a black polyvinyl chloride (PVC) jacket. It is Type TC-ER, rated 1000V, and carries one 1 AWG bare copper grounding conductor in addition to the 4 circuit conductors.
Southwire 67223599 Technical Specs
Construction
| Conductor Size | 500 kcmil |
|---|---|
| Number of Conductors | 4 (grounding conductor not included) |
| Conductor Material | Class B compressed stranded bare copper per ASTM B3 and ASTM B8 |
| Strands per Conductor | 37 |
| Insulation | Cross-linked polyethylene (XLPE), Type XHHW-2 |
| Conductor Identification | 1-BLACK, 2-RED, 3-BLUE, 4-ORANGE |
| Grounding Conductor | One 1 AWG Class B compressed stranded bare copper conductor |
| Filler and Binder | Paper filler; polyester flat thread binder tape |
| Jacket | Polyvinyl chloride (PVC) |
| Jacket Colour | Black |
| Type Designation | TC-ER |
Dimensions and Weight
| Diameter Over Conductor | 0.789 in (2.00 cm) |
|---|---|
| Insulation Thickness | 65 mils (1.65 mm) |
| Jacket Thickness | 110 mils (2.79 mm) |
| Approx. Overall Diameter | 2.407 in (6.11 cm) |
| Copper Weight | 6498 lbs/1000 ft (9670 kg/km) |
| Approx. Total Weight | 7620 lbs/1000 ft (11340 kg/km) |
Electrical and Thermal Ratings
| Voltage Rating | 1000V |
|---|---|
| Conductor Temperature | 90°C normal operation in wet and dry locations; 130°C emergency overload; 250°C short circuit |
| Other Properties | Sunlight resistant; silicone free |
Standards
| ASTM B3 | Soft or Annealed Copper Wire |
|---|---|
| ASTM B8 | Concentric-Lay-Stranded Copper Conductors |
| UL 44 | Thermoset-Insulated Wires and Cables |
| UL 1277 | Electrical Power and Control Tray Cables |
| UL 1685 | Vertical-Tray Fire Propagation and Smoke Release Test |
| ICEA S-58-679 | Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE) |
| ICEA S-95-658 (NEMA WC70) | Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy |
| IEEE 1202 FT4 | Flame Test (70,000) BTU/hr Vertical Tray Test |
Southwire 67223599 Applications
- Wet and dry areas, in conduits, ducts, troughs and cable trays.
- Direct burial, and aerial runs supported by a messenger.
- Class I, II, and III, Division 2 per NEC Article 501 and 502.
- Exposed runs as Type TC-ER per NEC 336.10.
Images are for reference only. Specifications may change without notice — verify suitability for your application before purchase. The manufacturer's documentation controls.
Need a cut length, bulk pricing, or a spec sheet?
Our team quotes custom lengths and volume orders, usually same day.